Device Diagnostics - Siemens SIMOCODE pro Function Manual

Industrial controls, motor management and control devices, communication
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Tables, data records
3.5 Modbus data tables
3.5.2.5

Device diagnostics

Read-only access to the device diagnostics is possible from the register memory area with
function codes 03 and 04, or the coil memory area with function codes 01 and 02.
Max. data length per access: 16 registers.
Table 3- 76
Device diagnostics
Input/holding
Type
register
Address high/low
0x1C00
low
Bit
high
Bit
0x1C01
low
Bit
high
Bit
282
Discrete
Identifier
input / coil
address
0x1C00
Reserved
0x1C01
Reserved
0x1C02
Reserved
0x1C03
Reserved
0x1C04
Reserved
0x1C05
Reserved
0x1C06
Reserved
0x1C07
Reserved
0x1C08
Status - group fault
0x1C09
Status - General warning
0x1C0A
Status - Device
0x1C0B
Status - Bus
0x1C0C
Status - PLC/PCS
0x1C0D
Status - Current flowing
0x1C0E
Status - PE command Start_Pause pending
0x1C0F
Status - PE energy saving mode active
0x1C10
Status - On<<
0x1C11
Status - On<
0x1C12
Status - Off
0x1C13
Status - On>
0x1C14
Status - On>>
0x1C15
Status - Start active
0x1C16
Status - Interlocking time active
0x1C17
Status - Change-over pause active
0x1C18
Status - Runs in open direction
0x1C19
Status - Runs in close direction
0x1C1A
Status - FC
0x1C1B
Status - FO
0x1C1C
Status - TC
0x1C1D
Status - TO
0x1C1E
Status - Cold run TPF
0x1C1F
Status - OPO
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003