I&M2 - Installation Date; I&M3 - Comment - Siemens SIMOCODE pro Function Manual

Industrial controls, motor management and control devices, communication
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

3.5.2.11
I&M2 - Installation date
Read access to the I&M2 data is possible via function codes 03 and 04. Write access is
possible via function codes 06 and 16.
Max. data length per access: 13 registers.
Table 3- 82
I&M2 - Installation date
Input/holding register
Address
0x4040
0x4045
1) Access to the installation date via Modbus: read/write
3.5.2.12
I&M3 - Comment
Read access to the I&M3 data is possible via function codes 03 and 04. Write access is
possible via function codes 06 and 16.
Max. data length per access: 32 registers.
Table 3- 83
I&M3 - Comment
Input/holding register
Address
0x4060
0x4065 ... 0x407F
1) Access to the comment via Modbus: read/write
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Content
Reserved
Date
Content
Reserved
Comments
Size
10 byte
16 byte
Size
10 byte
54 byte
Tables, data records
3.5 Modbus data tables
Access
1)
r
r/w
Access
1)
r
r/w
293