Tables, data records
3.6 EtherNet/IP data tables
Attribute ID
Access
28
Get
29
Get
30
Get
31
Get
32
Get
33..39
Get
40..63
Get
64
Get
65
Get
66
Get
67
Get
68
Get
69
Get
70
Get
71
Get
72
Get
73
Get
74
Get
75
Get
76
Get
77
Get
78
Get
79
Get
80
Get
81
Get
82
Get
83
Get
84
Get
85
Get
86
Get
87
Get
88
Get
89..90
Get
1) S7 format:
0/4 mA = 0
20 mA = 27648
2) Representation of the "Thermal motor model":
Value always refers to symm. Trip level, representation in 2 % increments in bits 6 ... 0
(range 0 to 254 %), bit 7 shows unbalance (fixed level 50 %).
3) Representation in Kelvin.
330
Designation
EM+ - ground fault current
EM+ - last trip current
Active power P
Apparent power S
Reserved
Reserved
Reserved
AM2 - output
AM2 - input
AM2 - input 2
Reserved
TM2 - temperature
TM2 - temperature 1
TM2 - temperature 2
TM2 - temperature 3
Frequency
Reserved
Reserved
Reserved
Current I_max_A_F
Current I_avg_A_F
Current I_L1_A_F
Current I_L2_A_F
Current I_L3_A_F
Active power P_F
Apparent power S_F
Voltage UL1_F
Voltage UL2_F
Voltage UL3_F
Cos phi_F
Frequency_F
Reserved
Data type
Range
DINT
DINT
DINT
0..0x7FFFFFFF
DINT
0..0x7FFFFFFF
DINT
DINT[7]
INT[24]
INT
0 .. 32767
INT
0 .. 32767
INT
0 .. 32767
INT
INT
0 .. 32767
INT
0 .. 32767
INT
0 .. 32767
INT
0 .. 32767
INT
0 .. 32767
INT
DINT
DINT
DINT
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL[2]
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Unit
1 mA
1 mA
1 W
1 VA
See
1)
1 K see
3)
1 K see
3)
1 K see
3)
1 K see
3)
0.01 Hz
1 A
1 A
1 A
1 A
1 A
1 W
1 VA
1 V
1 V
1 V
1
1 Hz
SIMOCODE pro - Communication