Tables, data records
3.3 Tables, PROFIBUS data records
Byte.Bit Designation (PRM group)
45.0
Warning level 0/4-20 mA<
46.0
Trip delay P>
47.0
Warning delay P>
48.0
Trip delay P<
49.0
Warning delay P<
50.0
Trip delay cos phi<
51.0
Warning delay cos phi<
52.0
Trip delay U<
53.0
Warning delay U<
54.0
Trip delay 0/4-20 mA>
55.0
Warning delay 0/4-20 mA>
56.0
Trip delay 0/4-20 mA<
57.0
Warning delay 0/4-20 mA<
58.0
Delay limit 1
59.0
Delay limit 2
60.0
Delay limit 3
61.0
Delay limit 4
62.0
TM - Hysteresis
63.0
Max. star time
64.0
UVO time
65.0
Staggering time
66.0
Analog value recording - Sampling
rate
67.0
Calculation module 2 -
Denominator 1
68.0
Calculation module 2 - Numerator 2
69.0
Calculation module 1 - Denominator
70.0
Truth table 4 type 3I/1O
190
Type
Range
Unit
Byte
0 - 255
*128
Byte
0 - 255
100
ms
Byte
0 - 255
100
ms
Byte
0 - 255
100
ms
Byte
0 - 255
100
ms
Byte
0 - 255
100
ms
Byte
0 - 255
100
ms
Byte
0 - 255
100
ms
Byte
0 - 255
100
ms
Byte
0 - 255
100
ms
Byte
0 - 255
100
ms
Byte
0 - 255
100
ms
Byte
0 - 255
100
ms
Byte
0 - 255
100
ms
Byte
0 - 255
100
ms
Byte
0 - 255
100
ms
Byte
0 - 255
100
ms
Byte
0 - 255
1 K
Byte
0 - 255
1 s
Byte
0 - 255
100
ms
Byte
0 - 255
1 s
Byte
0 - 20
5%
Byte
0 - 255
Byte
0 - 255
Byte
0 - 255
Byte
0 -
11111111B
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Default Note
0
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
20
Star-delta starter
0
0
0
0
0
0
0
SIMOCODE pro - Communication
Information
AM1
UM(+)
UM(+)
UM(+)
UM(+)
UM(+)
UM(+)
UM(+)
UM(+)
AM1
AM1
AM1
AM1
BU2(+)
BU2(+)
BU2(+)
BU2(+)
TM1 MM
BU0 BU2(+)
BU2(+)
BU2(+)
BU2(+)
BU2(+)
BU2(+)
BU2(+)
BU0,
BU2(+)