3.3.2.5

Data record 69 - Process image input

Table 3- 27
Data record 69 - Process image input
Byte.
Designation
Bit
0.0
Cyclic send - Bit 0.0
0.1
Cyclic send - Bit 0.1
0.2
Cyclic send - Bit 0.2
0.3
Cyclic send - Bit 0.3
0.4
Cyclic send - Bit 0.4
0.5
Cyclic send - Bit 0.5
0.6
Cyclic send - Bit 0.6
0.7
Cyclic send - Bit 0.7
1.0
Cyclic send - Bit 1.0
1.1
Cyclic send - Bit 1.1
1.2
Cyclic send - Bit 1.2
1.3
Cyclic send - Bit 1.3
1.4
Cyclic send - Bit 1.4
1.5
Cyclic send - Bit 1.5
1.6
Cyclic send - Bit 1.6
1.7
Cyclic send - Bit 1.7
2.0
PLC/PCS analog Input 1
4.0
PLC/PCS analog input 2
6.0
PLC/PCS analog input 3
8.0
PLC/PCS analog input 4
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Default
(also see parameters)
Status - ON<
Status - Off
Status - ON>
Event - Overload
operation
Status - Interlocking
time active
Status - Remote mode
Status - General fault
Status - general
warning
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
PLC / PCS
Max. current I_max
analog FI
input 1
Not assigned
PLC / PCS
Not assigned
analog FI
Not assigned
input 2
3.3 Tables, PROFIBUS data records
Type
Information
Bit
BU0 BU1 BU2(+)
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Word Float BU0 , BU1,
BU2(+)
Word
BU0, BU2(+)
Word Float
Word
Tables, data records