Siemens SIMOCODE pro Function Manual page 107

Industrial controls, motor management and control devices, communication
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Request message frame
Slave
address
1 byte
0x10
Response message frame
Slave address
1 byte
0x10
Note
"Read/Write Multiple Registers" function
The "Read/Write Multiple Registers" function cannot be used for writing parameter values via
Modbus.
Writing of parameter values results in an execution time in SIMOCODE for writing
parameters to the internal memory during which this SIMOCODE cannot respond to a
communication request and/or the command "Read/Write Multiple Registers" cannot be
concluded.
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Function
Start
code
address
read
operation
1 byte
2 bytes
0x17
0x04 0x00 0x0004
Function code
1 byte
0x17
Number
Start
Number
of
address
of
registers
write
register
(read
operation
N (write
access)
access)
2 bytes
2 bytes
2 bytes
0x00
0x00
0x00
0x01
Number_bytes
Data
1 byte
Nx2 bytes
0x08
0x00 0x00
Communication
2.3 Modbus communication
Number
Data
CRC
of bytes
(write
(write
access)
access)
1 byte
Nx2bytes 2 bytes
0x02
0x00
0x24
CRC
2 bytes
0x00 0x00
107