Input/holding register
Address high/
Bit
low
low
0x439E
high
low
0x439F
high
low
0x43A0
high
low
0x43A1
high
low
0x43A2
high
low
0x43A3
high
low
0x43A4
high
low
0x43A5
high
low
0x43A6
0x43A7
0x43A8
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Designation
Type Range
Delay limit 2
Byte
Delay limit 3
Byte
Delay limit 3
Byte
TM - Hysteresis
Byte
Max. star time
Byte
UVO time
Byte
Staggering time
Byte
Trace - Pre-trigger
Byte
Calculator 2 -
Byte
Denominator 1
Calculator 2 -
Byte
Numerator 2
Calculator 1 -
Byte
Denominator
Truth table 4
Byte
type 3I/1O
Truth table 5
Byte
type 3I/1O
Truth table 6
Byte
type 3I/1O
Calculator 2 -
Byte
Numerator 1
Calculator 2 -
Byte
Denominator 2
DM-F - Test
Byte
requirement level
Part - Word
parameters
AM1 - Start value
Word 0 ...
output
AM1 - End value
Word 0 ...
output
TM1 - Trip level T>
Word 0 ...
Unit
Default Comments
0 ... 255
100
5
ms
0 ... 255
100
5
ms
0 ... 255
100
5
ms
0 ... 255
1 K
5
0 ... 255
1 s
20
0 ... 255
100
0
ms,
1 s,
10 s
0 ... 255
1 s
0
0 ... 20
5%
0
0 ... 255
0
0 ... 255
0
0 ... 255
0
0 ... 111
0
11111B
0 ... 111
0
11111B
0 ... 111
0
11111B
-128 ...
0
127
-128 ...
0
127
0 ... 255
Week 0
0
65535
27648
65535
1 K
0
65535
Tables, data records
3.5 Modbus data tables
Access
r/w
r/w
r/w
r
r
r
r
r
r
r
r
r
r
r
r/w
r/w
r/w
r/w
Value for 0/4 mA
r/w
Value for 20 mA
r/w
r/w
Info
1)
AM1