Siemens SIMOCODE pro Function Manual page 245

Industrial controls, motor management and control devices, communication
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Byte.
Designation (PRM group)
Bit
19.0
Monitoring the number of starts
- Response to overshoot
19.2
Monitoring the number of starts
- Response to prewarning
19.4
Motor operating hours
monitoring - Response
19.6
Motor stop time monitoring -
Response
20.0
External fault 1 - Response
20.2
External fault 2 - Response
20.4
External fault 3 – Response
20.6
External fault 4 - Response
21.0
Reserved
21.2
Basic unit - Debounce time
inputs
21.4
Timer 1 - Type
21.6
Timer 2 - Type
22.0
Signal conditioning 1 - Type
22.2
Signal conditioning 2 - Type
22.4
Non-volatile element 1 - Type
22.6
Non-volatile element 2 - Type
23.0
EM+
- monitoring
2)
23.2
EM+
- monitoring warning
2)
23.4
EM - response to an external
ground fault
23.6
EM - response to warning of an
external ground fault
24.0
Bit[4] - Parameters (24)
24.0
External fault 1 - Reset also by
24.4
External fault 2 - Reset also by
25.0
External fault 3 - Reset also by
25.4
External fault 4 - Reset also by
26.0
Limit monitor - Hysteresis for
limit monitoring
26.4
EM+
- hysteresis
2)
27.0
Parameter target version -
Part a
27.4
Parameter target version -
Part b
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Type Range
Unit
Bit[2] 0, 1, 2, 3
Bit[2] 0, 1, 2
Bit[2] 0, 1, 2
Bit[2] 0, 1, 2
Bit[2] 1, 2, 3
Bit[2] 1, 2, 3
Bit[2] 1, 2, 3
Bit[2] 1, 2, 3
Bit[2]
Bit[2] 0 - 3
10
ms
Bit[2] 0, 1, 2, 3
Bit[2] 0, 1, 2, 3
Bit[2] 0, 1, 2, 3
Bit[2] 0, 1, 2, 3
Bit[2] 0, 1, 2, 3
Bit[2] 0, 1, 2, 3
Bit[2] 0, 1, 2, 3
Bit[2] 0, 1, 2, 3
Bit[2] 1, 3
Bit[2] 0, 1, 2
Bit[4] 0 - 1111B
Bit[4] 0 - 1111B
Bit[4] 0 - 1111B
Bit[4] 0 - 1111B
Bit[4] 0 - 15
1 %
Bit[4] 0 - 15
1 %
Bit[4]
Bit[4]
3.4 Tables, PROFINET data records
Default Note
0
0
0
0
1
1
1
1
0
1
Offset 6 ms
0
0 = With closing delay,
1 = Closing delay with memory
0
2 = With opening delay
3 = With fleeting closing
0
0 = Non-inverting
1 = Inverting
0
2 = Edge rising with memory
0
3 = Edge falling with memory
0
0
0 = on
1 = on+
0
2 = run
3 = run+
1
0 = Disabled
1 = Signaling
0
2 = Warn
3 = Tripping
0101B
Bit[0] = Panel reset
Bit[1] = Auto-reset
0101B
Bit[2] = Remote reset
0101B
Bit[4] = OFF command reset
0101B
5
5
0
0
Tables, data records
Information
245

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents