Byte.Bit
Designation
134.0
Reserved
136.0
Reserved
138.0
Reserved
140.0
Reserved
144.0
Current I_max_F (float)
148.0
Current I_avg_F
152.0
Current I_L1_F
156.0
Current I_L2_F
160.0
Current I_L3_F
164.0
Active power P_F
168.0
Apparent power S_F
172.0
Voltage U1_F
176.0
Voltage U2_F
180.0
Voltage U3_F
184.0
Cos phi_F
188.0
Frequency_F
192.0
Reserved
1) S7 format:
0/4 mA = 0
20 mA = 27648
2) Representation of the "Thermal motor model":
Value always refers to symm. trip level,
representation in steps of 2% in bits 6 ... 0 (range 0 to 254%), bit 7 shows unbalance (fixed
level 50%).
3) Representation in Kelvin.
4) 3UF7510-1AA00-0 ground-fault module
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Type
Range
Byte[4]
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Byte[8]
Tables, data records
3.4 Tables, PROFINET data records
Unit
Information
1 A
UM+
1 A
UM+
1 A
UM+
1 A
UM+
1 A
UM+
1 W
UM+
1 VA
UM+
1 V
UM+
1 V
UM+
1 V
UM+
UM+
1 Hz
UM+