Tables, data records
3.3 Tables, PROFIBUS data records
Byte.Bit Designation (PRM group)
18.2
Warning response I<
18.4
Stalled rotor - Response
18.6
EM+
- response to sensor
1)
fault
19.0
Monitoring the number of
starts - Response to
overshoot
19.2
Monitoring the number of
starts - Response to
prewarning
19.4
Motor operating hours
monitoring - Response
19.6
Motor stop time monitoring
- Response
20.0
External fault 1 - Response
20.2
External fault 2 - Response
20.4
External fault 3 - Response
20.6
External fault 4 - Response
21.0
Reserved
21.2
Basic unit - Debounce time
inputs
21.4
Timer 1 - Type
21.6
Timer 2 - Type
22.0
Signal conditioning 1 - Type Bit[2] 0, 1, 2, 3
22.2
Signal conditioning 2 - Type Bit[2] 0, 1, 2, 3
22.4
Non-volatile element 1 -
Type
22.6
Non-volatile element 2 -
Type
23.0
EM+
- monitoring
2)
23.2
EM+
- monitoring warning Bit[2] 0, 1, 2, 3
2)
23.4
EM - response to an
external ground fault
23.6
EM - response to warning
of an external ground fault
24.0
Part - Bit[4] parameters
24.0
External fault 1 - Reset also
by
24.4
External fault 2 - Reset also
by
178
Type Range
Unit
Bit[2] 0, 1, 2
Bit[2] 0, 1, 2, 3
Bit[2] 0, 1, 2, 3
Bit[2] 0, 1, 2, 3
Bit[2] 0, 1, 2
Bit[2] 0, 1, 2
Bit[2] 0, 1, 2
Bit[2] 1, 2, 3
Bit[2] 1, 2, 3
Bit[2] 1, 2, 3
Bit[2] 1, 2, 3
Bit[2]
Bit[2] 0 - 3
10 ms
Bit[2] 0, 1, 2, 3
Bit[2] 0, 1, 2, 3
Bit[2] 0, 1, 2, 3
Bit[2] 0, 1, 2, 3
Bit[2] 0, 1, 2, 3
Bit[2] 1, 3
Bit[2] 0, 1, 2,
Bit[4] 0 -
1111B
Bit[4] 0 -
1111B
Default
Note
0
0
0
0
0
0
0
1
1
1
1
0
1
Offset 6 ms
0
0 = With closing delay
1 = Closing delay with
0
memory
2 = With opening delay
3 = With fleeting closing
0
0 = Non-inverting
1 = Inverting
0
2 = Edge rising with
0
memory
3 = Edge falling with
0
memory
0
0 = on
1 = on+
0
2 = run
3 = run+
1
0 = disabled
1 = signaling
0
2 = warn
3 = tripping
0101B
Bit[0] = Panel reset
Bit[1] = Auto-reset
0101B
Bit[2] = Remote reset
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Information
BU0 BU1 BU2(+)
BU0 BU1 BU2(+)
BU0 BU2(+)
BU0 BU1 BU2(+)
BU0 BU1 BU2(+)
BU0 BU1 BU2(+)
BU0 BU1 BU2(+)
BU0 BU1 BU2(+)
BU0 BU1 BU2(+)
BU0 BU1 BU2(+)
BU0 BU1 BU2(+)
BU0 BU1 BU2(+)
BU0 BU1 BU2(+)
BU0 BU1 BU2(+)
BU0 BU1 BU2(+)
BU0 BU1 BU2(+)
BU0 BU1 BU2(+)
BU0 BU1 BU2(+)
BU0 BU2(+)
BU0 BU2(+)
BU0 BU1 BU2(+)
BU0 BU1 BU2(+)
BU0 BU1 BU2(+)
BU0 BU1 BU2(+)
SIMOCODE pro - Communication

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents