Data Record 94 - Measured Values - Siemens SIMOCODE pro Function Manual

Industrial controls, motor management and control devices, communication
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Tables, data records
3.4 Tables, PROFINET data records
3.4.2.8

Data record 94 - measured values

Table 3- 59
Data record 94 - measured values
Byte.Bit
Designation
0.0
Reserved
4.0
Thermal motor model
5.0
Phase unbalance
6.0
cos phi
7.0
Reserved
12.0
Max. current I_max
14.0
Current I_L1
16.0
Current I_L2
18.0
Current I_L3
20.0
Last trip current
22.0
Time to trip
24.0
Cooling down period
26.0
Voltage U_L1
28.0
Voltage U_L2
30.0
Voltage U_L3
32.0
AM1 - output
34.0
AM1 - input
36.0
AM1 - input 2
38.0
Reserved
40.0
TM1 - max. temperature
42.0
TM1 - temperature 1
44.0
TM1 - temperature 2
46.0
TM1 - temperature 3
48.0
EM+
- ground-fault current
4)
50.0
EM+
- last trip current
4
52.0
Active power P
56.0
Apparent power S
60.0
Reserved
64.0
Reserved
92.0
Reserved
116.0
AM2 - output
118.0
AM2 - input 1
120.0
AM2 - input 2
122.0
Reserved
124.0
TM2 - max. temperature
126.0
TM2 - temperature 1
128.0
TM2 - temperature 2
130.0
TM2 - temperature 3
132.0
Frequency
238
Type
Range
Byte[4]
Byte
0 - 255
Byte
0 - 100
Byte
0 - 100
Byte[5]
Word
0 - 65535
Word
0 - 65535
Word
0 - 65535
Word
0 - 65535
Word
0 - 65535
Word
0 - 65535
Word
0 - 65535
Word
0 - 65535
Word
0 - 65535
Word
0 - 65535
Word
0 - 32767
Word
0 - 32767
Word
0 - 32767
Word
0 - 65535
Word
0 - 65535
Word
0 - 65535
Word
0 - 65535
Word
0 - 65535
Word
0 - 65535
D-word
0 - 0xFFFFFFFF
D-word
0 - 0xFFFFFFFF
Byte[14]
Byte[28]
Byte[24]
Word
0 - 32767
Word
0 - 32767
Word
0 - 32767
Word
0 - 65535
Word
0 - 65535
Word
0 - 65535
Word
0 - 65535
Word
0 - 65535
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Unit
Information
See
IM UM(+)
2)
1 %
IM UM(+)
1 %
UM(+)
1 % / I
IM UM(+)
s
1 % / I
IM UM(+)
s
1 % / I
IM UM(+)
s
1 % / I
IM UM(+)
s
1 % / I
IM UM(+)
s
100 ms
IM UM(+)
100 ms
IM UM(+)
1 V
UM(+)
1 V
UM(+)
1 V
UM(+)
See
AM1
1)
AM1
AM1
1 K see
TM1
3)
TM1
TM1
TM1
EM(+)
EM(+)
1 W
UM(+)
1 VA
UM(+)
See
AM2
1)
AM2
AM2
1 K see
TM2
3)
TM2
TM2
TM2
0.01 Hz
UM+
SIMOCODE pro - Communication

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents