Tables, data records
3.4 Tables, PROFINET data records
No.
Designation
34
Recovery time
35
Last trip current
36
TM1 - max. temperature
37
TM1 - temperature 1
38
TM1 - temperature 2
39
TM1 - temperature 3
40
Permissible starts - Actual value
41
Motor stop time
42
DM-F - Time until test required
43
EM+ - last trip current
44
AM1 - input 1
45
AM1 - input 2
46
AM1 - input 3
47
EM+ - ground fault current
48
Acyclic receive data - analog value
49
Cyclic receive data - analog value 1
50
Cyclic receive data - analog value 2
51
Number of parameterizations
52
Motor operating hours - H word
53
Motor operating hours - L word
54
Int. motor operating hours - H word
55
Int. motor operating hours - L word
56
Device operating hours - H word
57
Device operating hours - L word
58
Number of starts - H word
59
Number of starts - L word
60
Int. number of starts CW - H word
61
Int. number of starts CW - L word
62
Int. number of starts CCW - H word
63
Int. number of starts CCW - L word
64
Energy W - high word
65
Energy W - low word
66
Reserved
..
Reserved
69
Reserved
70
Active power P - H word
71
Active power P - L word
72
Apparent power S - H word
73
Apparent power S - L word
74
Reserved
..
Reserved
85
Reserved
220
Unit
100 ms
1 % / Is
1 K
1 K
1 K
1 K
1 h
1 week
1 mA
See 1)
See 1)
See 1)
1 mA
1 s
1 s
1 s
1 s
1 s
1 s
1 kWh
1 kWh
1 W
1 W
1 VA
1 VA
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Information
IM UM(+)
IM UM(+)
TM1
TM1
TM1
TM1
DM-F
EM+
AM1
AM1
UM(+)
UM(+)
SIMOCODE pro - Communication