2.1.5.4
Integration of SIMOCODE pro as a SIMATIC PDM object (DPV1 slave via GSD) in
STEP7 HW Config
SIMOCODE pro can be integrated as a PDM object into the STEP7 HW Config when
version 6.0 + SP1 or higher of the SIMATIC PDM (Process Device Manager) is installed.
This requires the PDM option "Integration in STEP7."
The following table describes how you can insert SIMOCODE pro as a PDM object in the
STEP7 HW Config from the hardware catalog.
Table 2- 10
SIMOCODE pro as a SIMATIC PDM object (DPV1 slave via GSD) in STEP7 HW Config
Step
STEP7, V5.1+SP2 and higher
1
Start STEP7 and open the "HW Config."
2
To integrate SIMOCODE pro as a PDM object, navigate to the "PROFIBUS DP > Switching Devices"
directory in the hardware catalog.
3
Enter "SIMOCODE pro C (PDM)," "SIMOCODE pro S (PDM)," or "SIMOCODE pro V (PDM)" on the
PROFIBUS.
For SIMOCODE pro S and SIMOCODE pro V only.
SIMOCODE pro S and SIMOCODE pro V can be integrated into two basic types (basic type 1 or basic
type 2) (see Chapter Cyclic data (Page 17)). The default setting is basic type 2.
If you wish to use "basic type 1," delete the default "basic type 2" module and insert "basic type 1" instead.
Only in conjunction with the fail-safe digital module DM-F PROFIsafe:
Insert the "PROFIsafe" module in the second position in addition to "Basic type 1" or "Basic type 2."
You will find more information about using the DM-F PROFIsafe in the manual SIMOCODE pro fail-safe
digital modules (https://support.automation.siemens.com/WW/view/en/50564852).
4
Check the set DP interrupt mode (DPV0 or DPV1) as well as the enable of the DPV-1 interrupts on the
properties page of the DP slave. These settings influence the evaluation of the diagnostics data and
interrupts (see Chapter Evaluating diagnostics data (Page 34) and Chapter "Timestamping" (standard
functions) in the operating manual).
5
Start SIMATIC PDM to create the device parameters by double clicking on the slave symbol (see Chapter
Parameter data during startup (Page 40)).
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Communication
2.1 PROFIBUS communication
31