Tables, data records
3.4 Tables, PROFINET data records
Byte.
Designation (PRM group)
Bit
28.0
Byte parameters (28)
28.0
Internal ground fault - Delay
29.0
Overload protection - Class
30.0
Motor protection - Delay with
overload operation
31.0
Motor protection - unbalance
protection level
32.0
Motor protection - Unbalance
protection - Delay in the event
of unbalance
33.0
Interlocking time
34.0
FB time
35.0
Trip level I>
36.0
Warning level I>
37.0
Trip level I<
38.0
Warning level I<
39.0
Stalled rotor level
40.0
Trip delay I>
41.0
Warning delay I>
42.0
Trip delay I<
43.0
Warning delay I<
44.0
Blocking delay
45.0
Monitoring the number of starts
- Permissible starts
46.0
Reserved
47.0
EM+
- delay
2)
246
Type Range
Unit
Byte
0 .. 255
100
ms
Byte
5, 7, 10 ..
35, 40
Byte
0 - 255
100
ms
Byte
0 - 100
1 %
Byte
0 - 255
100
ms
Byte
0 - 255
1 s
Byte
0 - 255
100
ms
Byte
0 - 255
4 %
/ I
s
Byte
0 - 255
4 %
/ Is
Byte
0 - 255
4 %
/ Is
Byte
0 - 255
4 %
/ Is
Byte
0 - 255
4 %
/ Is
Byte
0 - 255
100
ms
Byte
0 - 255
100
ms
Byte
0 - 255
100
ms
Byte
0 - 255
100
ms
Byte
0 - 255
100
ms
Byte
1 - 255
Byte
Byte
0 - 255
100
ms
Default Note
5
10
5
40
5
0
5
0 = disabled
0
0
0
0
0
5
5
5
5
5
1
0
0
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Information
IM UM(+)
IM UM(+)
IM UM(+)
IM UM(+)
IM UM(+)
IM UM(+)
IM UM(+)
IM UM(+)
IM UM(+)
IM UM(+)
IM UM(+)
IM UM(+)
IM UM(+)
IM UM(+)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents