3.5.2.14
Extended device parameters 1
Read access to the device parameters is possible from the register memory area with
function codes 03 and 04.
Individual parameter data (marked with the motor symbol in the "Info" column) can be written
via Modbus RTU via the register memory area with function codes 06 and 16. This function
can be used to adjust settings such as the rated motor current during operation of the motor.
The "SIMOCODE ES (TIA Portal)" software is nonetheless required for full parameterization
of the SIMOCODE pro V Modbus devices (see also Chapter "Commissioning with
Modbus RTU" in the SIMOCODE pro – System Manual
(https://support.industry.siemens.com/cs/ww/en/view/109743957)).
Max. data length per access: 72 registers.
Table 3- 85
Extended device parameters 1
Input/holding register
Address high/
Bit
low
0x4380
0x4382
high
0
1
2
3
4
5
6
7
low
0
1
2
3
4
5
6
7
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Designation
Type Range
Coordination
Byte
[4]
Part - Bit parameters
3UF50 compatibility
Bit
mode
3UF50 operating
Bit
mode
Reserved
Bit
Reserved
Bit
Reserved
Bit
Reserved
Bit
Reserved
Bit
Reserved
Bit
Reserved
Bit
Voltage measuring -
Bit
Type of load
OPD - Warnings
Bit
OPD - Faults
Bit
AM1 - Measuring
Bit
range input
AM1 - Measuring
Bit
range
Output
Reserved
Bit
Reserved
Bit
Unit
Default Comments
0, 1
0
0, 1
0
0
0
0
0
0
0
0
0, 1
0
0, 1
0
0, 1
1
0, 1
0
0, 1
0
0
0
Tables, data records
3.5 Modbus data tables
Access
r
r
0 = DPV0
r
1 = DPV1
r
r
r
r
r
r
r
0 = 3-phase
r
1 = 1-phase
0 = Do not
r
display
1 = Display
0 = 0 ... 20 mA
r
1 = 4 ... 20 mA
r
r
r
Info
1)
from E03
301