Communication
2.2 PROFINET communication
Diagnostics for process faults
All SIMOCODE pro monitoring functions with "trip" configured as their response are
transmitted with the "fault" diagnostics status.
Diagnostics for device faults
Diagnostics events that can occur in connection with defective hardware or incorrect
parameterization are also transmitted with the "fault" diagnostics status.
The response of the different monitoring functions can be configured individually. Depending
on the function, the following can be selected by configuration:
● Deactivated: There is no response. No diagnostics are produced.
● Signaling: The diagnostics event is entered in data record 92 and is displayed in the
"Faults/Warnings/Events" online dialog box of SIMOCODE ES. No diagnostics alarm is
triggered.
● Warning: A diagnostics alarm is generated with the "maintenance demand" diagnostics
status.
● Tripping: A diagnostics alarm is generated with the "fault" diagnostics status.
Evaluating diagnostics with SIMATIC S7 300/400 and STEP 7 V5
Diagnostics with STEP 7 HW Config
In the online display of STEP 7 HW Config, after selection of the corresponding module
(in this case: SIMOCODE pro V PN), the status of the module is determined with the
"module status" function.
The following statuses are represented in the overview:
Table 2- 12
Symbol representation
in HW Config Online
The detailed diagnostics is displayed as follows on the "IO device diagnostics" tab card
under "Channel-specific diagnostics":
Table 2- 13
Slot
1: I/O module
66
Module statuses in diagnostics with STEP 7 HW Config
Status in HW Config Online
Module does not exist
Module defective
Maintenance required
Maintenance required
OK
Detailed diagnostics with STEP 7 HW Config
Channel No.
0
Possible cause with SIMOCODE
SIMOCODE shut down or not
accessible on the bus
Fault is pending
Warning is pending
Event it pending
None
Error
Error text, e.g. "Execution of ON command"
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
SIMOCODE pro - Communication