Festo CiA 402 Manual page 148

For motor controller
Table of Contents

Advertisement

A
Diagnostic messages
Error group 22
PROFIBUS
No.
Code
Message
22-0
7500h
Error in PROFIBUS initialisation
Cause
Action
22-2
7500h
PROFIBUS communication error
Cause
Action
Error group 25
Firmware
No.
Code
Message
25-1
6081 h
Incorrect firmware
Cause
Action
Error group 26
Data flash
No.
Code
Message
26-1
5581h
Checksum error
Cause
Action
Error group 29
SD card
No.
Code
Message
29-0
7680h
No SD
Cause
Action
29-1
SD initialization error
7681h
Cause
Action
148
Fieldbus interface defective.
• Please contact Technical Support.
– Faulty initialisation of the Profibus interface.
– Interface defective.
• Check the set slave address.
• Check bus termination.
• Check wiring.
Motor controller and firmware are not compatible.
• Update the firmware.
Checksum error of a parameter set.
• Load factory setting.
• If the error is still present, the hardware may be defective.
An attempt was made to access a missing SD card.
Check:
• whether the SD card is inserted properly,
• whether the SD card is formatted,
• whether a compatible SD card is plugged in.
– Error during initialization.
– Communication not possible.
• Plug card back in.
• Check card (file format FAT 16).
• If necessary, format card.
Festo – GDCP-CMMS/D-C-CO-EN – 1404NH – English
Reaction
PS off
configurable
Reaction
PS off
Reaction
PS off
Reaction
configurable
configurable

Hide quick links: