Virtual Outputs - GE F650 Instruction Manual

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

5 SETTINGS
5.6.7.2 VIRTUAL INPUTS STATUS MONITORING:
Actual > Inputs/Outputs > Virtual Inputs > Virtual Input Latched > Virtual Input Self-Reset
Table 5–108: VIRTUAL INPUTS STATUS
VIRTUAL INPUTS LATCHED
LATCHED VIRT IP 1
LATCHED VIRT IP 2
...
LATCHED VIRT IP 32
Text assignment for virtual input is made at Setpoint > Relay Configuration > Virtual Inputs. It should be taken into
account that the text assigned for virtual inputs in the relay configuration screen are only for file management, they are not
sent to the relay.
There are 512 virtual outputs that may be assigned via Logic configuration. If not assigned, the output will be forced to OFF
(Logic 0). An ID may be assigned to each virtual output. Virtual outputs are resolved in each pass through the evaluation of
the logic equations. For more detailed information see chapters 5.9 and 5.10 in this manual.
There are 16 virtual outputs latched that may be assigned via Logic configuration. If not assigned, the output will be forced
to OFF (Logic 0). Virtual outputs are resolved in each pass through the evaluation of the logic equations. These virtual
outputs latched can only be assigned as an S/R output, they only will be linked to a PLC's S/R output and their values
remain after switching off- on the unit
These virtual output latched may be reset by a PLC setting as it is shown in the following figure
GEK-106310AB
VIRTUAL INPUTS SELF-RESET
SELF-RST VIRT IP 1
SELF-RST VIRT IP 2
...
SELF-RST VIRT IP 32
F650 Digital Bay Controller
5.6 INPUTS/OUTPUTS

5.6.8 VIRTUAL OUTPUTS

5.6.9 VIRTUAL OUTPUTS LATCHED
5
5-135