GE F650 Instruction Manual page 104

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

4 HUMAN INTERFACES. SETTINGS & ACTUAL VALUES 4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
Thanks to the use of a double flash memory, one with the Bootcode startup program and the operative system, and a
second one with the application program (firmware), a high reliability is guaranteed when updating the unit firmware, as
even if the case of a communication breakdown during the firmware upgrade process, we can retry the process for an
unlimited number of times.
• Upgrade 650 web server (Ethernet connection):Go to "Communications> Upgrade 650 web server". The relay web
server application can be updated to further versions (if available) using this menu without modifying the relay
operative system.
-
Upload info files to relay (Ethernet connection): Go to "Communications>Upload info files to relay". This
functionality is used to store setting files (*.650) inside the relay, as well as auxiliary files used by the programmable
logic graphical editor (*.pep, *.aut, *.lib).
-
Download info files from relay (Ethernet connection): Go to "Communications>Download info files from relay".
This functionality is used for retrieving the files (*.650 and *.pep, *.aut, *.lib) that have been previously stored in the
relay flash memory.
Important Note:
*.650 files contain protection, control settings, relay configuration and compiled logic
equations. This file can be retrieved from the relay, using the "File>Get info from
relay" option in EnerVista 650 Setup (through serial or Ethernet communication).
"File>Send info to relay" option stores this *.650 file in the relay.
*.pep, *.aut and *.lib files contain the logic configuration projects necessary to modify the
logic (virtual outputs) in the relay. These files can be stored in the relay, using the
"Communication>Upload info files to relay" option in EnerVista 650 Setup (through
Ethernet communication). They can be retrieved using "Communication>Download
info files to relay" option in EnerVista 650 Setup program (Ethernet communication).
Take into account that the *.pep, *.aut and library files are necessary to modify the PLC
logic (virtual outputs). Without these files setting and configuration can be modified but
not
logic
"Communication>Upload info files to relay" option to store these logic configuration
files into the relay.
It is important to distinguish between "Send / Get info to relay" and "Upload /
Download info files to/from relay". "File>Send/Get info to relay" sends/gets
settings and configuration and compiled logic equation to/from the relay (*.650 format),
and the relay automatically starts working with the new settings once they are stored.
"Communications>Upload/Download info files to relay", stores/retrieves in the
relay hard disk: settings, configuration and compiled logic equations (*.650) besides the
PLC files (*.pep, *.aut, *.lib). This is only a physical storage (file backup).