4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE 4 HUMAN INTERFACES. SETTINGS & ACTUAL VALUES
4.1.8.3 PROTECTION ELEMENTS
This option shows all the protection-grouped elements available in the relay as shown in Table 4.9:. Each of these groups
includes the specific protection units of the same type. For example phase currents group includes TOC, IOC, directional
units, etc. There are three groups available, so there are three protection units of each function that can work in grouped
mode or ungrouped (altogether).
Table 4.9: GENERAL OVERVIEW OF PROTECTION ELEMENTS MENU:
PROTECTION
ELEMENTS
4
Options enabled only in On-line mode are marked as (*). Options enabled only in Off-line mode are marked as (**)
Table 4.10: PROTECTION ELEMENTS INCLUDED
PHASE
CURRENT
NEUTRAL
CURRENT
GROUND
CURRENT
SENSITIVE
GROUND
CURRENT
4-18
Phase Current
All overcurrent grouped functions for phase current.
All overcurrent grouped functions for neutral current. (Calculated from
Neutral Current
phases, not measured)
All overcurrent grouped functions for ground current. (Measured from 4
Ground Current
current input)
All overcurrent grouped functions for sensitive ground current.
Sensitive Ground
Current
(Measured from 5
Negative Sequence
All Negative sequence overcurrent grouped functions.
Current
All voltage grouped functions for phases, neutral, ground and auxiliary
Voltage Elements
voltage
Forward power, directional power and wattmetric ground fault (High and
Power
Low) grouped protection functions.
Phase TOC High
Phase time overcurrent, high level (51PH)
Phase TOC Low
Phase time overcurrent, low level (51PL)
Phase IOC High
Phase instantaneous overcurrent, high level (50PH)
Phase IOC Low
Phase instantaneous overcurrent, low level (50PL)
Phase Directional
Phase directional unit (67P). Quadrature Voltage for polarization
Thermal Model
Thermal model or Thermal image unit for phases (49)
Neutral TOC
Neutral time overcurrent (51N)
Neutral IOC
Neutral instantaneous overcurrent (50N)
Neutral Directional
Neutral directional unit (67N). Voltage, current and dual polarization.
Ground TOC
Ground time overcurrent (51G)
Ground IOC
Ground instantaneous overcurrent (50G)
Ground Directional
Ground directional unit (67G). Voltage, current and dual polarization.
Sensitive Ground TOC
Sensitive ground time overcurrent (51SG).
Sensitive Ground IOC
Sensitive ground instantaneous overcurrent (50SG).
Isolated Ground IOC
Isolated ground overcurrent (50IG)
F650 Digital Bay Controller
th
current input)
th
GEK-106310AB