5.6 INPUTS/OUTPUTS
Configuration of settings relative to inputs and outputs can only be accessed through the EnerVista 650 Setup
software, and not via the HMI. For this purpose, the user must access Setpoint > Inputs/Outputs > Contact I/O > Board
X, being X the corresponding I/O board.
settings relative to I/O boards are described in Table 5–100:
Table 5–100: I/O BOARD SETTINGS
SETPOINT > INPUTS/OUTPUTS > CONTACT I/O >
BOARD F > BOARD G > BOARD H > BOARD J
SETTING DESCRIPTION
I/O board type (available only for CIO modules)
Input activation voltage threshold Group A
Input activation voltage threshold Group B
Input activation voltage threshold Group C
Input activation voltage threshold Group D
Debounce time for Group A
Debounce time for Group B
Debounce time for Group C
Debounce time for Group D
5
Input type
Input signal time delay
Output logic type
Output type
Output pulse length
Analog Inputs Range
Minimum Value
Maximum Value
Snapshot event generation
The snapshot event setting enables or disables the snapshot event generation for this element. It is mandatory to enable
this setting in order the input/output values to be refreshed in IEC61850 protocol
Being:
X
F, G, H or J, the I/O board name, depending on the Relay model.
F and G are internal Relay boards, and H and J are additional boards available in CIO modules (remote Bus CAN I/O
module).
5-118

5.6.2 CONTROL SETTINGS FOR INPUTS/OUTPUTS

NAME
I/O Board Type_X
Voltage Threshold A_X
Voltage Threshold B_X
Voltage Threshold C_X
Voltage Threshold D_X
Debounce Time A_X
Debounce Time B_X
Debounce Time C_X
Debounce Time D_X
Input Type_X_CCY (CCY)
Delay Input Time_X_CCY
(CCY)
Output Logic_X_0Z
Output Type_X_0Z
Pulse Output Time_X_0Z
Range_X_0Z
Min_Value_X_0Z
Max_Value_X_0Z
Snapshot Events
F650 Digital Bay Controller
DEFAULT
STEP RANGE
VALUE
NONE
N/A
[NONE,
16 INP + 8OUT,
8 INP + 8OUT + SUPV,
32 INP
16 INP + 8 ANA]
80
1 V
[10 : 230]
80
1 V
[10 : 230]
80
1 V
[10 : 230]
80
1 V
[10 : 230]
15
1 ms
[1 : 50]
15
1 ms
[1 : 50]
15
1 ms
[1 : 50]
15
1 ms
[1 : 50]
POSITIVE
N/A
[POSITIVE-EDGE,
NEGATIVE-EDGE,
POSITIVE,
NEGATIVE]
0
1 ms
[0 : 60000]
POSITIVE
N/A
[POSITIVE,
NEGATIVE]
NORMAL
N/A
[NORMAL,
PULSE,
LATCH]
10000
1 ms
[0 : 60000]
NONE
N/A
[NONE,
-1 to 0mA,
0 to 1 mA,
-1 to 1 mA,
0 to 5 mA,
0 to 10 mA]
0.00
0.01
[ -9999.99 : 9999.99]
0.00
0.01
[ -9999.99 : 9999.99]
ENABLED
N/A
[DISABLED –
ENABLED]
.