CHAPTER 5: SETTINGS
: "VO1"
OUTPUT H1a OPERATE
: "VO2"
OUTPUT H1a RESET

5.9.4 Virtual outputs

SETTINGS  INPUTS/OUTPUTS  VIRTUAL OUTPUTS  VIRTUAL OUTPUT 1(96)
 VIRTUAL OUTPUT 1
The virtual inputs and outputs are digital signals associated with UR-series internal logic signals. Virtual inputs include
signals generated by the local user interface. The virtual outputs are outputs of FlexLogic equations used to customize the
device. Virtual outputs can also serve as virtual inputs to FlexLogic equations.
There are 96 virtual outputs that can be assigned using FlexLogic. If not assigned, the output is forced to 'OFF' (Logic 0). An
ID also can be assigned to each virtual output. Virtual outputs are resolved in each pass through the evaluation of the
FlexLogic equations. Any change of state of a virtual output can be logged as an event if programmed to do so.
For example, if Virtual Output 1 is the trip signal from FlexLogic and the trip relay is used to signal events, the settings is
programmed as follows:
: "Trip"
VIRTUAL OUTPUT 1 ID
VIRTUAL OUTPUT 1 EVENTS

5.9.5 Resetting

SETTINGS  INPUTS/OUTPUTS  RESETTING
 RESETTING
Some events can be programmed to latch the faceplate LED event indicators, target messages, and/or graphical panel
annunciator windows. Once set, the latching mechanism holds all of the latched indicators or messages in the set state
after the initiating condition has cleared until a
latches) to the reset state where the initiating condition has cleared. The
button, a remote device via a communications channel, or any selected operand.
RESET
The three sources of
commands each activates the
RESET
command also creates its individual operand
the command. Each of these three operands generates an event in the event record when activated. The
setting here selects the operand that activates the

5.9.6 Direct inputs and outputs

5.9.6.1 Direct inputs
SETTINGS  INPUTS/OUTPUTS  DIRECT INPUTS  DIRECT INPUT 1(32)
 DIRECT INPUT 1
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
VIRTUAL OUTPUT 1 ID
Virt Op 1
VIRTUAL OUTPUT 1
EVENTS: Disabled
: "Disabled"
RESET OPERAND:
Off
command is received to return these latches (not including FlexLogic
RESET
RESET OP
RESET OP (PUSHBUTTON)
RESET OP (OPERAND)
DIRECT INPUT 1
NAME: Dir Ip 1
DIRECT INPUT 1
DEVICE ID: 0
DIRECT INPUT 1
BIT NUMBER:
0
DIRECT INPUT 1
DEFAULT: Off
Range: up to 20 alphanumeric characters
Range: Disabled, Enabled
Range: FlexLogic operand
command can be sent from the faceplate
RESET
FlexLogic operand. Each individual source of a
,
, or
RESET OP (COMMS)
RESET OP (OPERAND)
operand.
Range: up to 12 alphanumeric characters
Range: 0 to 16
Range: 0 to 32
Range: On, Off, Latest/On, Latest/Off
INPUTS/OUTPUTS
RESET
to identify the source of
RESET OPERAND
5-241