H.1 FACTORY DEFAULT SETTINGS
SETPOINT > PROTECTION ELEMENTS > POWER > DIRECTIONAL POWER>
DIRECTIONAL POWER 1> DIRECTIONAL POWER 2 > DIRECTIONAL POWER 3
SETTING DESCRIPTION
Function permission
Block from off-line
Directional Angle for stage 1
Pickup level for stage 1
Trip time for stage 1
Directional Angle for stage 2
Pickup level for stage 2
Trip time for stage 2
Snapshot Event generation
SETPOINT > CONTROL ELEMENTS > SETTING GROUP
SETTING DESCRIPTION
Setting Grouping Permission
Active Group
Snapshot Event generation
SETPOINT > CONTROL ELEMENTS > UNDERFREQUENCY
UNDERFREQUENCY 1 > UNDERFREQUENCY 2 > UNDERFREQUENCY 3
SETTING DESCRIPTION
Function permission
Pickup level
Trip time
Reset time
Minimum voltage threshold
Snapshot event generation
H
H-14
NAME
DEFAULT VALUE
Function
DISABLED
Blk Time After Close
0.00
Dir Power Angle 1
0.00
Stage 1 Tap
10.00
Stage 1 Time
60.00
Dir Power Angle 2
0.00
Stage 2 Tap
20.00
Stage 2 Time
60.00
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Active Group
GROUP 1
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Pickup Level
49.50
Trip Delay
0.00
Reset Delay
0.00
Minimum Voltage
30
Snapshot Events
ENABLED
F650 Digital Bay Controller
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.01 s
[0.00 : 900.00]
0.01 Deg
[0.00 : 359.99]
0.01MW
[-10000.00 : 10000.00]
0.01 s
[0.00 : 900.00]
1 Deg
[0.00 : 359.99]
0.01MW
[-10000.00 : 10000.00]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
[GROUP 1 – GROUP 2 –
N/A
GROUP 3]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.01 Hz
[20.00 : 65.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
1 V
[10 : 300]
N/A
[DISABLED – ENABLED]