5.4 PROTECTION ELEMENTS
5.4.4.3 NEUTRAL DIRECTIONAL ELEMENT (67N)
The Neutral directional element is used for supervising the neutral (3I0) overcurrent elements. This element can be set to
use either the neutral voltage, or the polarization current measured by the 5
magnitude.
Table 5–48: 67N ELEMENT SETTINGS
SETPOINT > PROTECTION ELEMENTS > NEUTRAL CURRENT > NEUTRAL DIRECTIONAL >
NEUTRAL DIRECTIONAL 1> NEUTRAL DIRECTIONAL 2 > NEUTRAL DIRECTIONAL 3
SETTING DESCRIPTION
Function permission
Maximum Torque Angle
Operation Direction
Polarization type
Block logic type
Polarization voltage threshold
Snapshot event generation
Settings for this element are:
Maximum Torque Angle (MTA):
5
Directional element direction (Direction): This setting indicates the Direction for which the element will allow a trip.
Polarization type (Polarization):
Polarization Voltage Threshold
Snapshot Events:
5-58
NAME
DEFAULT VALUE STEP
Function
DISABLED
MTA
-45
Direction
FORWARD
Polarization
VO
Block Logic
PERMISSION
Pol V Threshold
10
Snapshot Events
ENABLED
Angle used to rotate the polarization voltage. Positive angles are counter clockwise
rotations, and negative angles are clockwise rotations. The polarization magnitude,
once rotated, defines the MTA line. Vn rotated by this angle points to the semi plane
that corresponds to a Reverse fault. -Vn rotated this angle points to the semi plane
that corresponds to a Forward fault. A typical setting can be –45º.
Depending on this setting, the element will be activated for faults in the forward
direction, or ion the reverse direction, allowing its use in tripping or blocking
schemes. Possible options for this setting are FORWARD and REVERSE.
This setting indicates the type of Polarization to be used. The relay can use voltage
polarization (V0), and/or current polarization (Ip). Possible setting values are:
V0
Voltage polarization
Ip
Current polarization
V0 + Ip
Voltage or current polarization. This allows the element to
operate when any of the polarization magnitudes allow operation.
V0 * Ip
Voltage and current polarization. This allows the element to
operate when both polarization magnitudes allow operation.
If the selected polarization type is V0+Ip, then the relay will operate when any of the
polarization magnitudes indicate the selected direction in the Direction setting.
If the selected polarization type is V0*Ip, then the relay will only operate when both
polarization magnitudes indicate the selected direction in the Direction setting.
This is the minimum voltage considered for the direction calculation. Under this
setting, the element will be blocked.
The snapshot event setting enables or disables the snapshot event generation for
this elements.
F650 Digital Bay Controller
5 SETTINGS
th
current input (Ip), or both as polarization
RANGE
N/A
[DISABLED – ENABLED]
1 Deg
[-90 : +90]
N/A
[FORWARD – REVERSE]
N/A
[V
– I
– V
+I
– V
*I
0
P
0
P
0
N/A
[BLOCK – PERMISSION]
1 V
[0 : 300]
N/A
[DISABLED – ENABLED]
GEK-106310AB
]
P