7 IEC 61850 PROTOCOL
2.2.4.3 neuPTOV
This logical node class is used for neutral overvoltage and has 6 instances inside the device.
PTOV class
Attribute
Attribute
Name
Type
PTOV
Data
Common Logical Node Information
Mod
INC
Beh
INS
Health
INS
NamPlt
LPL
Status Information
Str
ACD
Op
ACT
Blk
ACT
Settings
StrVal
ASG
OpDlTmms
ING
RsDlTmms
ING
PTOVEna
SPG
Note: ACT includes origin attribute in ST, this is implemented according to Tissue 68.
GEK-106310AB
Explanation
Overvoltage
Mode
Behaviour
Health
Name plate
Start
Operate
Block
Start Value
Operate Delay Time
Reset Delay Time
Function TOV enable
F650 Digital Bay Controller
7.2 IEC 61850 PROFILE FOR F650
M/O/E
Notes
M
Status-only
M
M
M
M
TOV PKP
O
TOV OP
E
TOV BLK
O
Pickup Level (3 – 300)
O
Trip Delay ( 0 – 900000 )
Units in miliseconds
O
Reset Delay ( 0 – 900000 )
Units in miliseconds
E
Function