10.2 OUT OF SERVICE SETTING

10 COMMISSIONING
10.2OUT OF SERVICE SETTING
The unit has the Relay Out Of Service setting only configured at the general settings element. The unit has also an Out
Of service Status that it is only configured at Relay configuration > Protection elements tab. These states act stopping
all the changes on PLC equations and functions, even stopping all the changes in the input/output boards, so if there is a
change in any of the input or output the unit will not show this change until the unit has been set again in ready mode. For
example if an output is closed and the unit goes to out of service state, the output will be kept closed even though the state,
that makes it to close, change to open the output. When the unit goes out of the out of service state the output will be
opened if it was a change.
When the Out of Service status goes to ON, or the setting has been changed to Enabled, the ready led will also change to
red color. Be careful if ready led is linked to an output, because the output will not change its state. To set outputs to ready
state see factory default Logic & Configuration in the detailed manual. Take notice that, in the default configuration, the
general setting out of service is set to enable so it is necessary to change to disabled to start working with the unit
The following figure shows the flow chart of these states