GE F650 Instruction Manual page 753

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

F.1 IEC 60870-5-103 PROTOCOL
3.
Function Type
FUNCTION TYPE UI8 [1..8] <0..255>
<0..127>:= private range
<128..129>:= compatible range
<130..143>:= private range
<144..145>:= compatible range
<146..159>:= private range
<160..161>:= compatible range
<162..175>:= private range
<176..177>:= compatible range
<178..191>:= private range
<192..193>:= compatible range
<194..207>:= private range
<208..209>:= compatible range
<210..223>:= private range
<224..225>:= compatible range
<226..239>:= private range
<240..241>:= compatible range
<242..253>:= private range
<254..255>:= compatible range
F
F650 device is identified at the protocol level as "overcurrent protection", so the Function Type <160> will be used for all the
digital and analogues points proposed by the standard and mapped in this profile. For the other data supported by the
device, the customer will have the capability to use them, setting a number from the private range.
4.
Information Number
INFORMATION NUMBER := UI8 [1..8] <0..255>
Monitor direction := <0..255>
<0..15>:=system functions
<16..31>:= status
<32..47>:=supervision
<48..63>:=earth fault
<64..127>:=short circuit
<128..143>:=auto-reclosure
<144..159>:=measurands
<160..239>:=not used
<240..255>:=generic functions