GE F650 Instruction Manual page 775

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

H.1 FACTORY DEFAULT SETTINGS
SETPOINT > PROTECTION ELEMENTS > PHASE CURRENT >
> PHASE TOC HIGH > PHASE TOC HIGH 1> PHASE TOC HIGH 2 > PHASE TOC HIGH 3
> PHASE TOC LOW > PHASE TOC LOW 1 > PHASE TOC LOW 2 > PHASE TOC LOW 3
SETTING DESCRIPTION
Function permission
Input type
Pickup level
Curve shape
Time Dial
Reset type
Voltage Restraint
Snapshot Event generation
SETPOINT > PROTECTION ELEMENTS > PHASE CURRENT >
> PHASE IOC HIGH > PHASE IOC HIGH 1> PHASE IOC HIGH 2 > PHASE IOC HIGH 3
> PHASE IOC LOW > PHASE IOC LOW 1 > PHASE IOC LOW 2 > PHASE IOC LOW 3
SETTING DESCRIPTION
Function permission
Input type
Pickup level
Trip time
Reset time
Snapshot event generation
SETPOINT > PROTECTION ELEMENTS > PHASE CURRENT > PHASE DIRECTIONAL >
PHASE DIRECTIONAL 1> PHASE DIRECTIONAL 2 > PHASE DIRECTIONAL 3
SETTING DESCRIPTION
Function permission
Maximum Torque Angle
Operation Direction
Block logic
Polarization voltage threshold
Snapshot event generation
H
SETPOINT > PROTECTION ELEMENTS > PHASE CURRENT > THERMAL MODEL >
THERMAL MODEL 1> THERMAL MODEL 2 > THERMAL MODEL 3
SETTING DESCRIPTION
Function permission
Heating constant
Cooling constant
Pickup level
Alarm level
Snapshot event generation
H-8
NAME
DEFAULT VALUE
Function
DISABLED
Input
PHASOR(DFT)
Pickup Level
1.00
Curve
IEEE Ext Inv
TD Multiplier
1.00
Reset
INSTANTANEOUS
Voltage Restraint
DISABLED
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Input
PHASOR(DFT)
Pickup Level
30.00
Trip Delay
0.00
Reset Delay
0.00
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
MTA
45
Direction
FORWARD
Block Logic
PERMISSION
Pol V Threshold
40
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Heat Time Constant
6.0
Cool Time Constant
2.00
Pickup Level
1.00
Alarm Level
80.0
Snapshot Events
ENABLED
F650 Digital Bay Controller
STEP
RANGE
N/A
[DISABLED – ENABLED]
N/A
[PHASOR – RMS]
0.01 A
[0.05 : 160.00]
N/A
[See list of curves]
0.01 s
[0.00 : 900.00]
[INSTANTANEOUS –
N/A
LINEAR]
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
N/A
[PHASOR – RMS]
0.01 A
[0.05 : 160.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
1 Deg
[-90 : +90]
N/A
[FORWARD – REVERSE]
N/A
[BLOCK – PERMISSION]
1 V
[0 : 300]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.1 min
[3.0 : 600.0]
0.01 times
Heat Time
[1.00 : 6.00]
Ct.
0.01 A
[0.05 : 160.00]
0.10%
[1.0 : 110.0]
N/A
[DISABLED – ENABLED]
APPENDIX H
USER
VALUE
USER
VALUE
USER
VALUE
USER
VALUE
GEK-106310AB

Advertisement

Table of Contents
loading

Table of Contents