H.1 FACTORY DEFAULT SETTINGS
SETPOINT > PRODUCT SETUP > DEMAND
SETTING DESCRIPTION
Function permission
Demand method for current values
Demand method for Power values
Demand interval
Trigger Enabled
Snapshot Event generation
SETPOINT > SYSTEM SETUP > GENERAL SETTINGS
SETTING DESCRIPTION
Phase CT ratio
Ground CT ratio
Sensitive ground CT ratio
Phase VT ratio
Phase VT connection
Rated voltage
Rated Frequency
Phase rotation
Frequency reference
Auxiliary Voltage
Snapshot Event generation
RELAY Out of service STATUS
SETPOINT > SYSTEM SETUP > FLEX CURVES
FLEX CURVES A > FLEX CURVES B> FLEX CURVES C > FLEX CURVES D
SETTING DESCRIPTION
Values for reset points 0.00 pkp
Values for reset points 0.05 pkp
...
H
Values for reset points 0.97 pkp
Values for reset points 0.98 pkp
Values for operation points 1.03 pkp
Values for operation points 1.05 pkp
...
Values for operation points 19.50 pkp
Values for operation points 20.00 pkp
H-6
NAME
DEFAULT VALUE
Demand Function
DISABLED
CRNT Demand
THERMAL
Method
EXPONENTIAL
POWER Demand
THERMAL
Method
EXPONENTIAL
Demand Interval
5 Minutes
Trigger Enabled
DISABLED
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Phase CT Ratio
1.0
Ground CT Ratio
1.0
Stv Ground CT Ratio
1.0
Phase VT Ratio
1.0
Phase VT Connection WYE
Nominal Voltage
100.0
Nominal Frequency
50 Hz
Phase Rotation
ABC
Frequency Reference VI
Auxiliary Voltage
VX
Snapshot Events
DISABLED
RELAY OOS STATUS ENABLED
NAME
DEFAULT VALUE
Time 0.00xPKP [RST] 0.000
Time 0.05xPKP [RST] 0.000
...
...
Time 0.97xPKP [RST] 0.000
Time 0.98xPKP [RST] 0.000
Time 1.03xPKP [OP]
0.000
Time 1.05xPKP [OP]
0.000
...
...
Time 19.50xPKP [OP] 0.000
Time 20.00xPKP [OP] 0.000
F650 Digital Bay Controller
STEP
RANGE
N/A
[DISABLED – ENABLED]
[BLOCK INTERVAL -
ROLLING DEMAND -
N/A
THERMAL
EXPONENTIAL]
[BLOCK INTERVAL -
ROLLING DEMAND -
N/A
THERMAL
EXPONENTIAL]
N/A
[5 – 10 – 15 – 20– 30–60]
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
STEP
RANGE
0.1
[1.0 : 6000.0]
0.1
[1.0 : 6000.0]
0.1
[1.0 : 6000.0]
0.1
[1.0 : 6000.0]
N/A
[WYE – DELTA]
0.1
[1.0 : 250.0]
Hz
[50-60]
N/A
[ABC – ACB]
N/A
[VI-VII-VIII]
N/A
[VX – VN]
N/A
[DISABLED – ENABLED]
N/A
DISABLED-ENABLED
STEP
RANGE
0.001 s
[0.000 : 65.535]
0.001 s
[0.000 : 65.535]
0.001 s
[0.000 : 65.535]
0.001 s
[0.000 : 65.535]
0.001 s
[0.000 : 65.535]
0.001 s
[0.000 : 65.535]
0.001 s
[0.000 : 65.535]
0.001 s
[0.000 : 65.535]
0.001 s
[0.000 : 65.535]
0.001 s
[0.000 : 65.535]
APPENDIX H
USER
VALUE
USER
VALUE
USER
VALUE
GEK-106310AB