4 HUMAN INTERFACES. SETTINGS & ACTUAL VALUES 4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
Table 4.7: GENERAL OVERVIEW OF COMMUNICATION SETTINGS MENU:
COMMUNICATION
SETTINGS
Serial Ports
Network (Ethernet)
ModBus Protocol
DNP3 Slave
IEC 870-5-104
SNTP (*)
PROCOME
IEC 870-5-103
Options enabled only in On-line mode are marked as (*). Options enabled only in Off-line mode are marked as (**)
4.1.8.2 SYSTEM SETUP
This section shows the settings related to the system setup definition such as shown in the following table.
Table 4.8: GENERAL OVERVIEW OF SYSTEM SETUP MENU:
SYSTEM
SETUP
General Settings
Flex Curves
Breaker settings
Breaker maintenance
Switchgear
Options enabled only in On-line mode are marked as (*). Options enabled only in Off-line mode are marked as (**)
GEK-106310AB
Baud rate and parity for COM1 and COM2 serial communication ports.
Ethernet communication parameters for COM3 (IP Address, Netmask,
Gateway IP)
NOTE: The ModBus Slave address used by Ethernet ports is the one set
for COM2.EnerVista 650 Setup software allows programming two
different Ethernet addresses, but the first IP has always to be set as the
second IP Address is an Alias.
ModBus Slave Addresses for serial and Ethernet communication and the
ModBus port number used for ModBus TCP/IP
Physical port, Slave Address for DNP, IP Addresses for Masters, TCP/
UDP Port, Unsolicited Response parameters, Analog scale factors and
deadbands, message fragment size, Binary input block.Available for
standard and IEC61850 models.
TCP Port, Common Addr of ASDU, Cyclic Meter Period and,
Synchronization Event settings.Available for standard and IEC61850
models.
Synchronization over Ethernet settings
Comm port and slave number for procome protocol. Only available for
procome models (5).
Com port, slave number and synchronization time out for IEC 103
protocol
This screen describes and enables the settings of the power system
where the relay will operate. Some of these settings will be used only for
metering values presentation purposes; however, some of them apply
directly to the sampling and analog-digital conversion process (rated
frequency setting). Therefore, these settings need to be adjusted so that
they fit the system settings.
Flex Curves – Programmable user curves: The relay incorporates 4
user curves called Flex Curve A, B, C and D. The points for these curves
are defined by the user in "Setpoint>System Setup>Flex Curves>Edit
Curve" menu in EnerVista 650 Setup. User defined flex curves can be
selected as an operation curve in all the time overcurrent functions in the
relay.
Breaker settings, maintenance and switchgear selection of the device
configured as breaker in the F650. The selected switchgear will be used
in recloser, breaker failure and synchronism functions. The settings are
Number of Switchgear, Maximum KI
Openings, Max.Openings 1 hour and Snapshot Events.
These settings correspond to the initialization of (KI)
counting of number of openings and closings of the switchgear
configured as breaker. These Counters allow the breaker Maintenance.
They are used to cumulate the breaker ageing produced by a trip or a
breaker opening. In order to incorporate the breaker historic, in case of
existing breakers, the system allows assigning an initial value to
accumulated amperes, and to the number of opening and closing
operations.
Configuration of snapshot events for each switchgear (enable or disable)
F650 Digital Bay Controller
2
2
t, KI
t Integ. Time, Maximum
2
t counters, and the
4
4-17