5.3 SYSTEM SETUP
OUT OF SERVICE
FLOWCHART
START
5.3.1.2 LOCAL - REMOTE BLOCK SETTING OVERVIEW
5
In the enhanced HMI with USB port new setting has been released in order to be able to lock the Local/Remote front key.
This setting is available via COMS or frontal HMI menu. The settings could be locked by password, so the operator wouldn't
be able to change the local-remote without inserting the password.
5.3.1.2.1 DEFINITIONS
The value is defined as:
OFF: The operator is able to change the operations from local to remote or OFF.
ON: The operator is not able to change the operations from local to remote or OFF.
5.3.1.2.2 SETTINGS
The unit will be set by the HMI and by 650Pc software as it is shown in the following figure.
5-24
RELAY IN
SERVICE
SETTING:
Relay Out
Disabled
Of Service
Enabled
RELAY OUT
Only if there is any
OF SERVICE
change from Disabled to
Enabled
Ready
LED OFF
F650 Digital Bay Controller
Only if there is any change from Enabled to
Disabled
Only if LOGIC:
Relay Out Of Service
goes from Enabled to
Disabled
Ready
OoS status
LED ON
OFF
LOGIC:
Relay Out
Of Service
Enabled
Only if there is a change
from Disabled to Enabled
OoS status
ON
5 SETTINGS
Disabled
GEK-106310AB