System Setup; General Settings - GE F650 Instruction Manual

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

5 SETTINGS

5.3SYSTEM SETUP

This section shows the settings related to the system setup definition.
This section determines the settings of the element configuration regarding its connection to the power system.
Access to these settings using the EnerVista 650 Setup software is at Setpoint > System Setup > General settings.
The corresponding settings are shown on the table below:
Table 5–20: GENERAL SETTINGS
SETPOINT > SYSTEM SETUP > GENERAL SETTINGS
setting Description
Name
Phase CT ratio
Phase CT Ratio
Ground CT ratio
Ground CT Ratio
Sensitive ground CT ratio
Stv Ground CT Ratio
Phase VT ratio
Phase VT Ratio
Phase VT connection
Phase VT Connection
Rated voltage
Nominal Voltage
Rated Frequency
Nominal Frequency
Phase rotation
Phase Rotation
Frequency reference
Frequency Reference
Auxiliary Voltage
Auxiliary Voltage
Snapshot Event generation
Snapshot Events
Relay Out of Service
Relay Out of Service
Local/Remote Blocked
Local/Remote Blocked
The system rated voltage is used as reference by the voltage restraint in the phase timed overcurrent element.
The Frequency reference marks the voltage channel to which the system Frequency is measured.
The auxiliary voltage setting can be selected between VN and VX.
VN means that all elements using neutral voltage will take the value directly from the fourth voltage input.
VX means that all elements using neutral voltage will take the value calculated from phase voltages.
5.3.1.1
OUT OF SERVICE SETTING
The unit has the Relay Out Of Service setting only configured at the general settings element. The unit has also an Out Of
service Status that it is only configured at Relay configuration > Protection elements tab. These states act stopping all the
changes on PLC equations and functions, even stopping all the changes in the input/output boards, so if there is a change
in any of the input or output the unit will not show this change until the unit has been set again in ready mode. For example
if an output is closed and the unit goes to out of service state, the output will be kept closed even though the state, that
makes it to close, change to open the output. When the unit goes out of the out of service state the output will be opened if
it was a change.
Functions affected by Out of service State
- IO Boards.
- PROTECTIÓN:
o Generator:
§ Generator Unbalance (46 gen)
GEK-106310AB
Default Value
1.0
1.0
1.0
1.0
WYE
100.0
50 Hz
ABC
VI
VX
DISABLED
ENABLED
OFF
F650 Digital Bay Controller
5.3 SYSTEM SETUP

5.3.1 GENERAL SETTINGS

Step
Range
0.1
[1.0 : 6000.0]
0.1
[1.0 : 6000.0]
0.1
[1.0 : 6000.0]
0.1
[1.0 : 6000.0]
N/A
[WYE – DELTA]
0.1
[1.0 : 250.0]
N/A
[50-60]
N/A
[ABC – ACB]
N/A
[VI-VII-VIII]
N/A
[VX – VN]
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
N/A
[ON -OFF]
5
5-21