APPENDIX H
SETPOINT > CONTROL ELEMENTS > PULSE COUNTERS
SETTING DESCRIPTION
Pulse counter enabling setting
Name of the pulse counter
Multiplier factor for the pulse counter
Overflow value for the pulse counter
Board selection for the pulse counter
Input index inside the selected board
Note: X is the pulse counter index, up to 8.
SETPOINT > CONTROL ELEMENTS > ANALOG COMPARATORS
SETTING DESCRIPTION
Generic Analog Function Permission
Generic Snapshot Events Generation
Analog Input Value Selection
Analog Maximum Threshold Value
Analog Minimum Threshold Value
Analog Delay for Activation Signal
Analog Hysteresis for the Deadband
Analog Direction for Activation Inside
or Outside the Deadband
Note: X is the analog comparator index, up to 20
SETPOINT > CONTROL ELEMENTS > FREQUENCY RATE OF CHANGE
FREQUENCY RATE OF CHANGE 1 > FREQUENCY RATE OF CHANGE 2 > FREQUENCY RATE OF CHANGE 3
SETTING DESCRIPTION
Function Permission
Direction of the frequency change
Operation Value in Hz/s
Minimum required voltage in %
nominal voltage
Minimum Frequency Threshold
Maximum Frequency Threshold
Frequency rate Trip Delay
Snapshot Events Generation
SETPOINT > CONTROL ELEMENTS > LOAD ENCROACHMENT
LOAD ENCROACHMENT 1 > LOAD ENCROACHMENT 2 > LOAD ENCROACHMENT 3
SETTING DESCRIPTION
Function Permission
Minimum positive-sequence voltage
required
Impedance reach of the element
Angle (Size of the blocking region)
Trip Time
Reset Time
Snapshot Events Generation
GEK-106310AB
NAME
DEFAULT VALUE
CntPulses Enabled X
DISABLED
CntPulses Name X
Pulse Counter 1
CntPulses Factor X
1.000
CntPulses Overflow X 65535
CntPulses Board
F
Origin X
CntPulses Input Origin
1
X
NAME
DEFAULT VALUE
Analog Function
DISABLED
Analog Snapshot
DISABLED
Events
Analog Input X
None
Analog Maximum X
1.000
Analog Minimum X
1.000
Analog Delay X
0.00
Analog Hysteresis X
1.0
Analog Direction X
OUT
NAME
DEFAULT VALUE
Function
DISABLED
Freq. Rate Trend
INCREASING
Freq. Rate Pickup
0.50
Freq. Rate OV Supv
40.00
Freq. Rate Min
45.00
Freq. Rate Max
65.00
Freq. Rate Delay
0.00
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Min. Voltage
25.00
Reach
1.00
Angle
5
Pickup Delay
0.000
Reset Delay
0.000
Snapshot Events
ENABLED
F650 Digital Bay Controller
H.1 FACTORY DEFAULT SETTINGS
STEP
RANGE
N/A
[DISABLED – ENABLED]
N/A
N/A
0.001
[0.000 : 65000.000]
1
[0 : 1000000]
N/A
[F,G,H,I]
1
[1 : 32]
STEP
RANGE
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
N/A
[All available analog values]
0.001
[-100000.000 : 100000.000]
0.001
[-100000.000 : 100000.000]
0.01 s
[0.00 : 900.00]
0.1
[0.0 : 50.0]
N/A
[IN-OUT]
STEP
RANGE
N/A
[DISABLED – ENABLED]
[INCREASING -
N/A
DECREASING - BI-
DIRECTIONAL]
0.01 Hz/s
[0.10 : 10.00]
0.01%
[0.00 : 110.00]
0.01 Hz
[20.00 : 80.00]
0.01 Hz
[20.00 : 80.00]
0.01 s
[0.00 : 60.00]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.01 V
[0.00 : 300.00]
0.01 Ohm
[0.02 : 250.00]
1 Deg
[5 : 50]
0.001 s
[0.000 : 65.535]
0.001 s
[0.000 : 65.535]
N/A
[DISABLED – ENABLED]
USER
VALUE
USER
VALUE
USER
VALUE
H
USER
VALUE
H-17