GE F650 Instruction Manual page 152

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

5 SETTINGS
PRODUCT SETUP>COMMUNICATION SETTINGS >DNP3 SLAVE
DNP3 SLAVE 1 > DNP3 SLAVE 2 > DNP3 SLAVE 3
Binary Input Block 6
Binary Input Block 7
Binary Input Block 8
Binary Input Block 9
Binary Input Block 10
5.2.1.5 IEC 60870-5-104
Communication settings for IEC 60870-5-104 protocol. For more detailed information go to appendix D in this manual.
DNP protocol is available for standard and IEC61850 models but it is not available procome models.
Table 5–6: IEC 60870-5-104 PROTOCOL SETTINGS
PRODUCT SETUP > COMMUNICATION SETTINGS >IEC 870-5-104
Name
Function
TCP Port
Common Addr of ASDU
Cyclic Meter Period
Synchronization Event
5.2.1.6 SNTP
Table 5–7: SNTP PROTOCOL SETTINGS
PRODUCT SETUP > COMMUNICATION SETTINGS >SNTP
Name
Function
UDP Port
Server Ip Oct1
Server Ip Oct2
Server Ip Oct3
Server Ip Oct4
The F650 supports the Simple Network Time Protocol specified in RFC-2030. With SNTP, the F650 can obtain the clock
time over an Ethernet network. The F650 acts as an SNTP client to receive time values from an SNTP/NTP server, usually
a dedicated product using a GPS receiver to provide an accurate time. Three different modes of SNTP operation are
supported. These modes are unicast, broadcast and anycast.
If SNTP functionality is enabled at the same time as an IRIG-B source is connected to the F650, the IRIG-B signal provides
the time value to the F650 clock for as long as a valid signal is present. If the IRIG-B signal is removed, the time obtained
from the SNTP server is used.
To use SNTP in unicast mode, Server IP Oct1...4 must be set to the SNTP/NTP server IP address. Once this address is
set and the Function setting is "UNICAST", the F650 attempts to obtain time values from the SNTP/NTP server. Since
many time values are obtained and averaged, it generally takes forty seconds until the F650 clock is synchronized with the
SNTP/NTP server. It may take up to one minute for the F650 to signal an SNTP FAIL state if the server is off-line.
GEK-106310AB
CTL EVENTS 81-96
CTL EVENTS 97-112
CTL EVENTS 113-128
SWITCHGEAR 1-8
SWITCHGEAR 9-16
Default Value
DISABLED
2404
255
0
0
Default Value
DISABLED
123
0
0
0
0
F650 Digital Bay Controller
N/A
N/A
N/A
N/A
N/A
Step
Range
N/A
[DISABLED-UNICAST–
BROADCAST- ANYCAST]
1
[1 : 65535]
1
[0 : 65535]
1
[0 : 3600]
1
[0 : 3600]
Step
Range
N/A
[DISABLED – ENABLED]
1
[1 : 65535]
1
[0 : 255]
1
[0 : 255]
1
[0 : 255]
1
[0 : 255]
5.2 PRODUCT SETUP
5
5-5

Advertisement

Table of Contents
loading