5.4 PROTECTION ELEMENTS
Polarization magnitudes can be, as in the case of 67N, Polarization voltage (3Vo), either calculated from the phase
voltages or measured from terminals A11-A12, or polarization current (Ip), measured from the fifth input transformer
terminals, Isg, terminals B11-B12.
The following table shows the used magnitudes in each of the Polarization possibilities:
Table 5–55: USED MAGNITUDES ACCORDING TO THE POLARIZATION SETTING
POLARIZATION SETTING
Vo
Ip
Vo + Ip
Vo * Ip
The following table shows the management of the element output signals (block and permission) depending on the
Polarization Type setting.
Table 5–56: OUTPUT SIGNALS MANAGEMENT ACCORDING TO THE POLARIZATION TYPE SETTING
POLARIZATION SETTING
Vo
Ip
Vo + Ip
5
Vo * Ip
The configuration of the signals required for blocking the Ground overcurrent elements from the signals provided by the
Ground directional element is made at Setpoint > Relay Configuration > Protection Elements using inverted operation
signals to block the trip.
For example, to block the ground time delayed elements:
GROUND TOC1 BLOCK = NOT (GROUND DIR1 OP)
GROUND TOC2 BLOCK = NOT (GROUND DIR2 OP)
GROUND TOC3 BLOCK = NOT (GROUND DIR3 OP)
To block the Ground Instantaneous elements:
GROUND IOC1 BLOCK = NOT (GROUND DIR1 OP)
GROUND IOC2 BLOCK = NOT (GROUND DIR2 OP)
GROUND IOC3 BLOCK = NOT (GROUND DIR3 OP)
5-64
OPERATION MAG.
Ig
Ig
Ig
Ig
GROUND DIR BLOCK SIGNAL
V
< Ajs. POL V THRESHOLD
0
I
< 5 mA
P
V
< POL V THRESHOLD
0
I
< 5 mA
P
V
< POL V THRESHOLD
0
I
< 5 mA
P
F650 Digital Bay Controller
5 SETTINGS
POLARIZATION MAG.
3V0
Isg
3V0 or Isg
3V0 and Isg
GROUND DIR OP SIGNAL
Permission V
0
Permission I
P
Permission V
0
Permission I
P
Permission V
0
Permission I
P
GEK-106310AB