7.3 IEC 61850 CONFIGURATOR
7 IEC 61850 PROTOCOL
Configuration of the reception part of GOOSE
In order to configure in F650 reception of configurable GOOSE it is necessary to have ICD/CID file of sending IED(s). It
means that first transsmision GOOSE has to completely set up in the sender and after that the ICD/CID has to be imported
to "IEC 61850 Configurator" tool of F650.
In IED list panel please right click with the mouse and select "Add IED" to include a new IED for GOOSE reception.
7
Figure 7–29: EXAMPLE OF GOOSE RECEPTION CONFIGURATION
After pressing a "ADD IED" a window will appear to select *.icd or *.cid file from disk, there is also the possibility to import
the icd file from and SCD.
When working with different devices it is advisable to set the IED Name to the position name of the device, to avoid having
different IEDs with the same IED name
After including the icd files from the devices which the relay is going to receive the data the user can map the data to the
remote inputs or to rinGGIO.
GOOSE configurable values can be mapped either to remote inputs or to rinGGIO tabs.
GOOSE fixed values can only be mapped to the remote inputs tab