11.3 EXAMPLE 3: PROCEDURE TO SET AN OPERATION
11.3EXAMPLE 3: PROCEDURE TO SET AN OPERATION
11
This simple operation describes how to program and set an operation command on the F650 relay. In the present case the
operation is:
To configure some F650 output contact to be operated since the front of the relay.
To set some LED to show the operation of the output contact (while being closed).
To close a F650 output contact using a front key pushbutton.
To reset the output contact and LED using another front key pushbutton.
Set the following values:
Under
SETPOINT CONTROL ELEMENTS INPUTS/OUTPUTS BOARD F
* This setting is non-relevant since it applies only when "pulse" type is chosen
Under
SETPOINT RELAY CONFIGURATION OUTPUTS
SELECT
Contact Output Operate 00 (Board F)
Contact Output Reset 00 (Board F)
Under
SETPOINT RELAY CONFIGURATION LEDS
11-8
NAME
Output Logic_00_00
Output Type_00_00
Pulse Output Time
SELECT
NAME
Close Contact_00_00
Led 14
F650 Digital Bay Controller
11 APPLICATION EXAMPLES
11.3.1 DESCRIPTION OF THE EXERCISE
VALUE
Positive
Latch
10000ms *
NAME
C_Output Oper_00_00
C_Output Reset_00_00
SOURCE
C_Output_00_00
11.3.2 PROCEDURE
SOURCE
Operation_bit000
Operation_bit001
GEK-106310AB