5.13 IEC 60870-5-103 PROTOCOL CONFIGURATION
5 SETTINGS
5.13IEC 60870-5-103 PROTOCOL CONFIGURATION
The IEC103 Configuration option will only be available if the F650 that supports this protocol (3 in the ordering code for
protocol selection). The IEC103 protocol for the F650 can be configured using the EnerVista 650 Setup program in the
menu Setpoint>IEC103 Configuration.
When opening the IEC103 configuration tool, the program will ask to open an existing "f650iec103.cfg" configuration file, if
this option is cancelled, the user will enter in the IEC103 configuration tool with no file selected. There is the possibility to
retrieve the IEC103 configuration from the relay pressing "Retrieve Configuration" button and start working with it. The user
can save the changes to the configuration file, and send it to the relay pressing "Send Configuration" button. In order to
start working with the new IEC103 configuration, the relay must be switched off and on.
The IEC103 slave can be identified (besides the slave number) with a long name (8 characters identifier) and with a sort
name (4 characters identifier for the manufacturer's internal software release) that can be set in the IEC103 configuration
file.
The control data that can be configured are: digital states, measurands and commands. The user can configure some
IEC103 parameters in the configuration file and then send this file to the relay
Digital states:
All the digital states that F650 supports, will be available in order to be mapped using the EnerVista 650 Setup program. All
5
the mapped information will be send as a respond to a general interrogation.
In the interoperability table, the states that the standard propose have been selected with the suitable information number.
Some of them must be generated in the firmware code as an OR operation. This information is mapped by default, but the
user can delete them if desired. For the other states, the customer can assign the Information Number <1..255> and the
Function Type <0..255>, but the Identification Type 1 (Time-tagged message) is fixed.
First of all, to configure a new mapping of a digital state, the user must set the Function Type and the Information number.
Then select the "Digital Status" option from the first combo box in the "Status" frame for mapping a single digital state, and
the digital state to be sent to the IEC103 master from the second combo box. On the other hand, the customer can
configure a logic OR operation of digital states selecting the "Logic" option from the first combo box and pressing the "Press
for Logic" button. In the screen that will appear, the user can choose the digital status combination to be sent to the IEC103
master. Then Press the "Save" button.
Finally press the "Add" button and the configured data will be added to the Status List.
If the user wants to remove an existing signal from the status list, select the signal with the mouse and then press on the
"Remove" button and the signal will be removed from the status list.
In the same way, if the user wants to change a configured signal from the status list, select the signal with the mouse, make
the changes and then press on the "Update" button and the signal will be updated in the status list
To save the data in the configuration file, press the "Save" button and all the data will be stored in the corresponding "*.cfg"
file.
5-172
F650 Digital Bay Controller
GEK-106310AB