Virtual Outputs; Resetting - GE C30 Instruction Manual

Controller system
Hide thumbs Also See for C30:
Table of Contents

Advertisement

INPUTS/OUTPUTS
Write the following FlexLogic equation (EnerVista example shown).
Program the Latching Outputs by making the following changes in the
OUTPUTS  CONTACT OUTPUT H1a
OUTPUT H1a OPERATE
OUTPUT H1a RESET

5.8.4 Virtual outputs

SETTINGS  INPUTS/OUTPUTS  VIRTUAL OUTPUTS  VIRTUAL OUTPUT 1(96)
 VIRTUAL OUTPUT 1
5
There are 96 virtual outputs that can be assigned using FlexLogic. If not assigned, the output is forced to 'OFF' (Logic 0). An
ID also can be assigned to each virtual output. Virtual outputs are resolved in each pass through the evaluation of the
FlexLogic equations. Any change of state of a virtual output can be logged as an event if programmed to do so.
For example, if Virtual Output 1 is the trip signal from FlexLogic and the trip relay is used to signal events, the settings is
programmed as follows:
VIRTUAL OUTPUT 1 ID
VIRTUAL OUTPUT 1 EVENTS

5.8.5 Resetting

SETTINGS  INPUTS/OUTPUTS  RESETTING
 RESETTING
Some events can be programmed to latch the faceplate LED event indicators and the target message on the display. Once
set, the latching mechanism holds all of the latched indicators or messages in the set state after the initiating condition
has cleared until a
The
command can be sent from the faceplate
RESET
programmed operand.
When the
command is received by the relay, two FlexLogic operands are created. These operands, which are stored
RESET
as events, reset the latches if the initiating condition has cleared. The three sources of
FlexLogic operand. Each individual source of a
RESET OP
,
(PUSHBUTTON)
RESET OP (COMMS)
selects the operand that creates the
5-154
menu (assuming an H4L module):
: "VO1"
: "VO2"
VIRTUAL OUTPUT 1 ID
Virt Op 1
VIRTUAL OUTPUT 1
EVENTS: Disabled
: "Trip"
: "Disabled"
RESET OPERAND:
Off
command is received to return these latches (not including FlexLogic latches) to the reset state.
RESET
or
to identify the source of the command. The
RESET OP (OPERAND)
RESET OP (OPERAND)
SETTINGS  INPUTS/OUTPUTS  CONTACT
Range: up to 12 alphanumeric characters
Range: Disabled, Enabled
Range: FlexLogic operand
button, a remote device via a communications channel, or any
RESET
command also creates its individual operand
RESET
operand.
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
commands each create the
RESET
RESET OP
setting here
RESET OPERAND