5.12 PROCOME CONFIGURATION
The user must select the digital signals to be sent to the PROCOME master configuring the identifier number (Procome ID)
for each of them. Take into account that this procome ID is the bit in which is set the digital signal configured in that ID, for
example, it the contact input 1 from the board G is configured to the Procome ID 10, the signal 10 will be located in the byte
1 bit 2 of the answer sent by the procome slave.
To configure a new signal, set the procome ID selected for that signal, select the digital signal in the combo box that will
appear and the press the "Add" button, that signal will be added to the status list signals configured in the procome
configuration file. If the user wants to remove an existing signal from the status list, select the signal with the mouse and
then press on the "remove" button and the signal will be removed from the status list. To save the data in the configuration
file, press the "save" button and all the data will be stored in the "f650procome.cfg" file.
Analog Measurements:
In the measurements configuration screen, for each measurement selected the configuration signals are:
Procome ID: which is the identification number for each measurement
Identifier: it is the measurement selected to be sent in the procome slave answer
Factor: it is the multiplier factor to be applied to the relay measurement to make the final measurement calculation to
be sent to the master
Offset: it is an offset factor to be applied to the relay measurement to make the final measurement calculation to be
sent to the master
The Factor and offset parameters allow the user to perform different scaling in the relay measurements. The final
measurement sent to the procome master will be: a*x+b, where x is the relay measurement, a is the multiplier factor and b
is the offset.