GE F650 Instruction Manual page 237

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

5.5 CONTROL ELEMENTS
5.5.4.1 VOLTAGE INPUTS
In order to perform the synchronism check function, the F650 uses only one voltage from each end of the breaker. Voltage
values to be compared must be on the same basis, either phase-to-phase or phase-to-ground voltage; they must be the
same at both ends of the breaker; it is not possible to compare a phase-to-ground voltage at one end with a phase-to-
phase voltage at the other end.
Additionally, if on one end, three voltages have been connected, the necessary voltage on the other end for Function 25 will
only be single-phase voltage. If there is only one voltage (either phase-to-phase or phase-to-ground) at both ends of the
breaker, this must be from the same phase in both cases.
The selection of voltage values to be used by the synchronism element is made in the relay General settings:
V1 is the line voltage, selectable from the relay voltage channels, using the "Frequency Reference" setting at
Setpoint > System Setup > General settings > Frequency Reference. (Please refer to the voltage correspondence
Table 5–76:)
V2 is the busbar voltage measured at the auxiliary voltage input (terminals A11-A12). To enable the busbar voltage
metering in the relay, it is required to select VX in the Auxiliary Voltage setting at Setpoint > System Setup >
General settings > Auxiliary Voltage.
The voltage correspondence is detailed in the following table:
Table 5–76: VOLTAGE CORRESPONDENCE ELEMENT 25
Setpoint>System Setup>General settings>Frequency Reference
Voltage selection for element 25 of F650
Setpoint>System Setup>General settings>Phase VT Connection=WYE
5
Phase-to-ground voltage connection.(Wye connection)
Setpoint>System Setup>General settings>Phase VT Connection=DELTA
Phase-to-phase voltage connection.(Delta connection).
Setpoint>System Setup>General settings>
Auxiliary Voltage=Vx
Setpoint > System Setup > General settings > Auxiliary Voltage setting must be set to Vx, in order to monitor auxiliary
voltage instead of Vn (neutral voltage, coming from an open delta connection).
5.5.4.2 APPLICATION
Even if the application range of the F650 is quite wide and the element can be used in distribution lines at any voltage level,
it must be taken into account that it is a three-pole tripping relay, designed for managing a single breaker. This is why
F650 is not suitable for one and a half breaker configurations, or ring configurations where a transmission line or feeder has
two breakers.
5-90
F650 Digital Bay Controller
5 SETTINGS
VOLTAGE CORRESPONDENCE
V
V
V
I
II
III
V
V
V
a-g
b-g
c-g
V
V
V
a-b
b-c
c-a
V
x
GEK-106310AB

Advertisement

Table of Contents
loading

Table of Contents