11.2 EXAMPLE 2: TOC PROTECTION + RECLOSING SETTINGS PROCEDURE
11
Under
SETPOINT  CONTROL ELEMENTS  AUTORECLOSE
Under
SETPOINT  CONTROL ELEMENTS   OTHER FUNCTIONS   SYNCHROCHECK
The synchrocheck function and its permission to close is a condition in the present exercise to allow the recloser to give the
different programmed shots. Should not this condition be required these settings are non relevant, but if does like in the
present case the synchrocheck function must be set as follows
The programmed operation of a TOC protection with reclosing and synchrocheck features for the F650 relay is shown in
F650 Tripping and reclosing scheme Figure 11–1: Some conclusions follows:
The recloser cycle ends at lockout status since a permanent fault remains after two unsuccessful reclosing trials.
The holding time for reclosing conditions can be very low since the processor internal time to check them is instantaneously
if they are present at this moment. Depending in the application reclosing conditions might come later especially when
commands are sent from dispatching center. If does then this timing must be set properly.
11-6
NAME
Function
Max. Number of shots
Dead Time 1
Dead Time 2
Dead Time 3
Dead Time 4
Reclaim Time
Condition Permission
Hold Time
Reset Time
NAME
Function
Dead Bus Level
Live Bus Level
Dead Line Level
Live Line Level
Max. Volt Difference
Max. Angle Difference
Max. Freq. Difference
Breaker Closing Time
DL-DB Function
LL-DB Function
DL-LB Function
Additional Comments on Scheme
F650 Digital Bay Controller
11 APPLICATION EXAMPLES

11.2.4 PROCEDURE TO SET THE RECLOSER

VALUE
Enabled
2
2.0s
4.0s
---
---
0.05s
Enabled
0.1s
1.9s

11.2.5 PROCEDURE TO SET THE SYNCHROCHECK

VALUE
Enabled
10V
50V
10V
50V
10
10º
20mHz
0.07s
Disabled
Disabled
Disabled
GEK-106310AB