GE F650 Instruction Manual page 426

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

7 IEC 61850 PROTOCOL
Additional Items:
Maximum number of GOOSE messages which could be
sent
Maximum number of GOOSE messages which could be
received
Interpretation of quality at subscriber side
Restrictions on Data Set elements for transmission
GOOSE
GSSE
Description
What elements of a subscribed GSSE header are checked
to decide the message is valid and the allData values are
accepted? If yes, describe the conditions. For example:
Destination MAC address = as multicast
SendingIED = valid reference, not NULL
timeAllowedtoLive > 0
numDatSetEntries = matches with number of datSet
members & allData members
What is the behaviour when one subscribed GSSE
message isn't received or syntactically incorrect (missing
GSSE)
What is the behaviour when one subscribed GSSE
message exceeds the previous time Allowed to Live (TAL)
What is the behaviour when a subscribed GSSE message
is out-of-order
What is the behaviour when a subscribed GSSE message
is duplicated
6 PIXIT for Control model
Description
What control modes are supported:
Is Time activated operate (operTm) supported
What is the behaviour of the DUT when the test attribute is
set in the SelectWithValue and/or Operate request
What are the conditions for the time (T) attribute in the
SelectWithValue and/or Operate request
Is "operate-many" supported
Is pulse configuration supported
What check conditions are supported
GEK-106310AB
4
8
Quality is not required to be in the data set. If configured in
data set and received its value is by default ignored.
However it is possibe to map quality to Bistring13 object at
subscriber side and then use any of its 13 bits.
Data Set elements for transmission GOOSE have to be
Data Attributes (leaf objects). The exception to this rule is
FixedGOOSE (only use between GE devices).
Value / Clarification
N source MAC address
Y destination MAC address
Y timeAllowedtoLive
Y SendingIED
N t
N stNum
N sqNum
Y numDatSetEntries
A single "missing" GSSE message is ignored.
It signals this GSSE as "offline".
Sequence number is ignored.
Sequence number is ignored.
Value / Clarification
Y status-only
Y direct-with-normal-security
Y sbo-with-normal-security
Y direct-with-enhanced-security
Y sbo-with-enhanced-security
Note: control models:
-sbo-with-normal-security
-direct-with-enhanced-security
-sbo-with-enhanced-security
are available only for Pos attribute in logical nodes XCBR
and CSWI
N
DUT ignores the test value and executes the command as
usual
DUT ignores the test value and executes the command as
usual.
N
N
N synchrocheck
N interlock-check
F650 Digital Bay Controller
7.2 IEC 61850 PROFILE FOR F650
7
7-57