GE F650 Instruction Manual page 54

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

2 PRODUCT DESCRIPTION
2.4.6.2 AC VOLTAGE INPUTS
VT Ratio
Rated Voltages
Metering range:
Relay Burden:
Voltage Withstand:
VAC inputs do not need varistors, as the impulse test is applied to 100% of the transformers
2.4.6.3 CONTACT INPUTS
Input Activation Voltage Threshold:
Impedance:
Maximum error:
Load for voltage supervision inputs:
Voltage threshold for voltage
supervision inputs:
Debounce Time:
Recognition time:
Timing resolution:
For Input Activation Voltage Threshold and Debounce Time there is a single setting for all inputs in the same group (inputs
sharing the same common).
Input Type and Delay Input Time are not grouped; there is a different setting for each input.
Input Type
Delay Input Time
2.4.6.4 REMOTE INPUTS (IEC61850 GSSE/GOOSE)
Number of input points:
Number of remote devices:
Default states on loss of comms:
2.4.6.5 ANALOG INPUTS
Input impedance
Current Input (mADC):
Conversion Range:
Accuracy:
Type:
GEK-106310AB
1.0 to 6000.0 in steps of 0.1
275 Vac
From 2 to 275 Vac
0.05 VA at 120 Vac (50 or 60 Hz)
Continuous at 275 V to neutral
1 min/hr at 420 to neutral
10 to 230 Vdc in steps of 1 V (selectable by setting)
> 100 kOhm
±10% setting or ± 5 V
2 mA + V/100 kOhm
< 10 V (fixed)
1 to 50 in steps of 1 ms
< 1ms
1 ms
Positive-Edge / Negative-Edge / Positive/ Negative
0 to 60000 ms in steps of 1 ms (Input signal time delay)
32, configured from 64 incoming bit pairs
16
On, Off, Latest/on, Latest/off
116Ω
0 to -1; 0 to +1; -1 to +1; 0 to 5; 0 to 10; 0 to 20; 4 to 20 (programmable)
-1 to +20mA
±0.2% of full scale
Passive
F650 Digital Bay Controller
2.4 TECHNICAL SPECIFICATIONS
2
2-25

Advertisement

Table of Contents
loading

Table of Contents