5 SETTINGS
Table 5–60: ISOLATED GROUND IOC ELEMENT SETTINGS
SETPOINT > PROTECTION ELEMENTS > SENSITIVE GROUND CURRENT > ISOLATED GROUND IOC
ISOLATED GROUND IOC 1> ISOLATED GROUND IOC 2 > ISOLATED GROUND IOC 3
SETTING DESCRIPTION
Function Permission
High Voltage
Low Current
Low Voltage
High Current
Operation time
Deviation time to instantaneous
Snapshot event generation
The relay settings for the Isolated Ground IOC elements are as follows:
Function:
Vh, VL, Ih, IL:
Operation time (Delay):
Deviation time to Instantaneous (Time to inst): Time after the trip during which the elements become instantaneous. It
Snapshot Events:
OPERATION PRINCIPLES:
Operation of the isolated Ground element is based on the detection of a current that exceeds the setting, with neutral
voltage supervision (3V0). This allows to set the element very sensitive, with a very low current level, ensuring that small
angle or ratio errors in the current transformers will not cause the relay to operate, as the neutral voltage verified is higher
than the one set.
Values for Ih, IL, Vh and VL, which define the relay operation area, are configurable. H magnitudes must be higher than L
magnitudes. The 50IG element can be supervised by directional element 67SG.
Using the relay input magnitudes In and Vn, if the point defined by (In, Vn) is inside the operation area and if the directional
element (if directional supervision is set) allows it, the element picks up and the set delay time starts counting down. If a
directional block appears during the countdown, the element is reset. After the set time the element trips. Once tripped, the
relay cannot be blocked by the directional element, and the trip remains while the fault exists.
After the trip, the deviation time to instantaneous starts to run, so that all pickups produced during this time will produce an
Instantaneous trip. This means that, if after a trip the breaker is reclosed and the fault persists or reappears, the trip will be
instantaneous. If the user doesn't want to use this function, then the Deviation Time to Instantaneous (Time to inst)
setting must be set to zero seconds. Once the time has expired, the element returns to its normal operation.
GEK-106310AB
NAME
DEFAULT VALUE STEP
Function
DISABLED
Vh Level
20
Il LEVEL
0.005
Vl LEVEL
2
Ih LEVEL
0.025
Delay
0.00
Time to inst
0.00
Snapshot Events
ENABLED
This setting determines whether the element is operative and can generate pickup
and trip events, which can be configured to close outputs, light up LEDs or trigger
oscillography.
Vn and In values that define the points in the operative area.
This is the selectable period between the element pickup and trip, with a range from
0 to 900 seconds in steps of 0,01 seconds.
must be set to zero if the functionality is not required.
The snapshot event setting enables or disables the snapshot event generation for
this element.
F650 Digital Bay Controller
5.4 PROTECTION ELEMENTS
RANGE
N/A
[DISABLED – ENABLED]
1 V
[2 : 70]
0.001 A
[0.005 : 0.400]
1 V
[2 : 70]
0.001 A
[0.005 : 0.400]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
5
5-67