H.1 FACTORY DEFAULT SETTINGS
SETPOINT > CONTROL ELEMENTS > BREAKER FAILURE
SETTING DESCRIPTION
Function permission
Supervision (retrip) pickup level
Hiset pickup level
Lowset pickup level
Internal arc pickup level
Internal arc time delay
Retrip time delay
Hiset time delay
Lowset time delay
Second stage time delay
WITHOUT current element time delay No Current Delay
Snapshot event generation
SETPOINT > CONTROL ELEMENTS > VT FUSE FAILURE)
SETTING DESCRIPTION
Function permission
Snapshot event generation
SETPOINT > CONTROL ELEMENTS > BROKEN CONDUCTOR
BROKEN CONDUCTOR 1 >BROKEN CONDUCTOR 2 >BROKEN CONDUCTOR 3
SETTING DESCRIPTION
Function permission
Tap Level in percentage of I2/I1
Trip Time
Snapshot event generation
Current Inhibition Level setting
SETPOINT > CONTROL ELEMENTS > LOCKED ROTOR
LOCKED ROTOR 1 >LOCKED ROTOR 2 >LOCKED ROTOR 3
SETTING DESCRIPTION
Function permission
Input type
H
Full load current
Pickup level
Trip time
Reset time
Snapshot event generation
H-16
NAME
DEFAULT VALUE
Function
DISABLED
Supervision Pickup
1.00
Hiset Pickup
5.00
Lowset Pickup
2.00
Internal Arc Pickup
0.10
Internal Arc Delay
10.00
Supervision Delay
10.00
HiSet Delay
10.00
LowSet Delay
10.00
2nd Step Delay
10.00
10.00
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Tap
20
Trip Delay
60
Snapshot Events
ENABLED
Operation Threshold
0.005
NAME
DEFAULT VALUE
Function
DISABLED
Input
PHASOR(DFT)
Full Load Current
0.50
Pickup Level
1.01
Trip Delay
0.00
Reset Delay
0.00
Snapshot Events
ENABLED
F650 Digital Bay Controller
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.01 A
[0.05 : 160.00]
0.01 A
[0.05 : 160.00]
0.01 A
[0.05 : 160.00]
0.01 A
[0.05 : 160.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.10%
[20.0 : 100.0]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
0.001 A
[0.000 : 1.000]
STEP
RANGE
N/A
[DISABLED – ENABLED]
N/A
[PHASOR – RMS]
KA
[0.10 : 10.00]
N/A
[1.01 : 109.00]
s
[0.00 : 900.00]
s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
APPENDIX H
USER
VALUE
USER
VALUE
USER
VALUE
USER
VALUE
GEK-106310AB

Advertisement

Table of Contents
loading