Inputs And Outputs; Digital Inputs - GE F650 Instruction Manual

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

10 COMMISSIONING

10.9INPUTS AND OUTPUTS

During all tests, the screw on the rear of the relay must be grounded.
During this test, the user will determine the activation/deactivation points for every input in the relay for the set voltage value
of 30 Volts.
Verify that the error does not exceed ± 10% (+10% on activation, -10% on deactivation).
Default board settings for the input test can be modified in EnerVista 650 Setup software in:
Setpoint>Inputs/Outputs>Contact I/O>Board X
X, will be substituted by the corresponding board:
F for board in first slot
G for board in second slot
H for board in first slot of CIO module
J for board in second slot of CIO module
Test settings for mixed board (type 1:16 inputs and 8 outputs):
I/O BOARD TYPE 1 (MIXED)
Voltage Threshold A_X
Voltage Threshold B_X
Debounce Time A_X
Debounce Time B_X
Input Type_X_CC1 (CC1)
...
Input Type_X_CC16 (CC16)
The inputs test is completed by groups of 8 inputs, as this type of board has 2 groups of 8 inputs with the same common.
For the first 8 inputs, the voltage threshold setting is determined by Voltage Threshold A. For the next 8 inputs, the setting
is Voltage Threshold B. Inputs (or contact converters, CC1 – CC16) must also be set to POSITIVE.
Test settings for mixed board (type 2: 8 digital inputs, 4 blocks for supervision and 8 outputs):
I/O BOARD TYPE 2 (SUPERVISION)
Voltage Threshold A_X
Voltage Threshold B_X
Debounce Time A_X
Debounce Time B_X
Input Type_X_CC1 (CC1)
...
Input Type_X_CC8 (CC8)
The inputs test is completed by groups of 4 inputs, as this type of board has 2 groups of 4 inputs with the same common.
For the first 4 inputs, the voltage threshold setting is determined by Voltage Threshold A. For the next 4 inputs, the setting
is Voltage Threshold B. Inputs (or contact converters, CC1 – CC8) must also be set to POSITIVE.
If the relay incorporates more input modules, these tests must also be applied to them.
GEK-106310AB
30 V
40 V
5 ms
5 ms
POSITIVE
...
POSITIVE
30 V
40 V
5 ms
5 ms
POSITIVE
...
POSITIVE
F650 Digital Bay Controller
10.9 INPUTS AND OUTPUTS

10.9.1 DIGITAL INPUTS

10-11
10

Advertisement

Table of Contents
loading

Table of Contents