GE F650 Instruction Manual page 81

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE 4 HUMAN INTERFACES. SETTINGS & ACTUAL VALUES
4.1.5.2 ON LINE MODE
NO
4
Save all settings & configuration ("File>Get info from relay")
Store in the relay the Logic configuration files (*.pep, *.aut, *.lib) as well as the
*.650 for further logic changes. ("Communication>Upload info files to relay")
4-8
Run EnerVista 650 Setup
Connect to the relay
("Communication>Computer>ON")
Modify and send to the
relay protection Settings
and relay configuration
Is it necessary to
program
additional logic?
NO
Is the relay
completely
configured?
Figure 4–4: ON LINE MODE FILE MANAGEMENT
F650 Digital Bay Controller
YES
Launch the Logic Configuration tool in EnerVista
650 Setup ("Setpoint>Logic Configuration")
Create new or modify the existing logic
("File>Open Project")
Compile ("Run>Compile")
and save logic file (*.pep) and drawing design
(*.aut) in Logic Configuration tool ("File>Save
Project")
Send logic to relay ("Run>Send Equations to
Relay") and Exit PLC Graphic Editor
YES
GEK-106310AB