5 SETTINGS
5.10 LOGIC CONFIGURATION (PLC EDITOR)
After creating the first timer, the second one for output deactivation is made. The set signal will be the virtual output created
as an output of the first timer (VO_100_OUTPUT_ACTIVATION), the reset signal will be the output of the second timer
(VO_100_OUTPUT_DEACTIVATION), the time delay is set as 200 ms.
Once the timing logic (timer 1 + timer 2) has been created, the activation signal (VO_100_OUTPUT_ACTIVATION) is linked
to several virtual outputs. Therefore, virtual outputs (VO_102_OUTPUT_1, VO_103_OUTPUT_2, VO_104_OUTPUT_3,
VO_105_OUTPUT_4) will be activated if the CONT IP_G_CC1(CC1) variable is set to 1. Once the
VO_100_OUTPUT_ACTIVATION is active, it will be deactivated after 200 ms, and will remain deactivated for 5 seconds.
This process will be repeated while the digital input is active.
To finish the process the logic must be compiled (Run >Compile) and the equations sent to the relay (Run >Send
Equations to relay) to start working with the new logic.
5
GEK-106310AB
F650 Digital Bay Controller
5-163