GE F650 Instruction Manual page 80

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

4 HUMAN INTERFACES. SETTINGS & ACTUAL VALUES 4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
Table 4.1: TYPES OF FILES GENERATED BY ENERVISTA 650 SETUP SOFTWARE OPERATION MODE OFF-LINE:
SETTINGS & CONFIGURATION FILE *.650
Description
Settings and Configuration Section
Created by
EnerVista 650 Setup
Relay configuration file containing all
Settings, input/output and LEDs configuration, graphic
Contents
display configuration, etc.
Equations corresponding to the logic created and
compiled in the PLC Editor
EnerVista 650 Setup:
How to save
"File>Save *"
EnerVista 650 Setup:
How to open
"File>Open *"
Connect with the relay
("Communications>Computer")
How to
Open the created file ("File>Open *")
transfer to
Send to relay from the menu: "File>Send info to relay"
relay
Note that texts used in the configuration of inputs,
outputs, etc. are not sent to the relay. The only texts
sent to relay are operations, events, and LEDs.
In case of using element libraries (either existing ("File Library>Open Library") or created by the user ("File Library>New
Library"), the program will create and manage the corresponding files (*.lib) in a folder named FDB (Functional Block
Diagram). These files are used for the PLC project compilation. It is necessary to store them with the other logic
configuration files that built the PLC project (*.pep, *.aut, *.lib).
Besides sending basic information to the relay (Settings + configuration) in *.650 format, it is recommended to store *.650,
*.pep, *.aut and *.lib files inside the relay ("Communication>Upload info files to relay"), to ensure that logic configuration
files will be available in the future for further logic modifications; either if these files are not used by the relay, they are
required for connecting to a relay and analyzing its configuration. The program manages the logic configuration files
globally, so that when the user selects to save file *.pep in the relay, the associated *.aut and *.lib files are also stored.
File storage inside the relay
(RECOMMENDED)
Retrieval of files stored in the relay
(RECOMMENDED)
GEK-106310AB
LOGIC CONFIGURATION FILES (*.PEP, *AUT, *.LIB)
*.PEP
Header for Logic
project
Logic configuration
graphic editor (PLC
Editor)
PLC project file
containing the
necessary
elements
information relative
to the relay model,
logic libraries
included in the
project (*.lib),
graphic file name
(*.aut), etc.
PLC Editor:
"File>Save
Project"
PLC Editor:
"File>Open
Project"
Connect with the relay ("Communications>Computer")
Launch Logic equations Editor ("Setpoint>Logic
Configuration")
Open the created PLC project ("File>Open Project")
Compile the project ("Run>Compile")
Now the logic (virtual outputs) can be sent directly to relay
("Run>Send Equations to Relay"). Texts of virtual outputs are
not stored in the relay, only in the logic configuration files to be
edited.
"Communication > Upload info files to relay" through Ethernet
"Communication > Download info files from relay" through Ethernet
F650 Digital Bay Controller
*.AUT
*.LIB
Graphical edition
container. Logic
User programmable
equations (Virtual
logic objects
Outputs) in FDB
format.
Logic configuration
Logic configuration
graphic editor (PLC
graphic editor (PLC
Editor)
Editor)
Library file to be
PLC Project file
included as an
containing all the
object in a PLC
drawings used by
project. Logic
the logic, required by
packages that can
650 relay based on
be stored into
IEC 61131-3
libraries and be
standard. Functional
distributed in
block diagram
different PLC
(FDB).
projects.
PLC Editor:
PLC Editor:
"File>Save
"File>Save
Project"
Library"
PLC Editor:
PLC Editor:
"File>Open
"File>Library>New
Project"
Library"
4
4-7

Advertisement

Table of Contents
loading

Table of Contents